Handling of 24 V DC input
■Input terminal
For FX5U CPU module, input module (extension cable type), input/output module (extension cable type), powered input/
output module and high-speed pulse input/output module
Sink input
When a no-voltage contact or NPN open collector transistor output
is connected between an input (X) terminal and the [0V] terminal
and the circuit is closed, the input (X) turns on.
The input display LED turns on.
Fuse
L
N
100 to 240 V AC
S/S
0V
24V
*1
X0
X1
X7
*1 Input impedance
RUN terminal setting
X0 to X17 of the CPU module can be used as RUN input terminals by
setting parameters.
MELSEC iQ-F FX5 User's Manual (Application)
For input module (extension connector type) and input/output module (extension connector type)
• Sink-input-dedicated type
When a no-voltage contact or NPN open collector transistor output is connected between an input (X) terminal and the [COM] terminal and the circuit is
closed, the input (X) turns on.
At this time, the LED corresponding to the DISP switch lights up.(FX5-C16EX/D does not have the DISP switch.)
*1
X0
X1
COM
*1 Input impedance
• Sink/source-input-common type
In the sink input, the input (X) is turned on by connecting 24 V DC [+] with
the [COM] terminal or [S/S] terminal, and connecting a no-voltage contact
or NPN open collector transistor output between the input terminal and 24
V DC to close the circuit.
At this time, the input display LED turns on. For the module having DISP
switch, LED complying with DISP switch turns on.
• Sink input wiring
*1
X0
X1
*2
COM
*1 Input impedance
*2 Depending on the module, the [COM] terminal is
[S/S] terminal.
Source input
When a no-voltage contact or PNP open collector transistor output
is connected between an input (X) terminal and the [24V] terminal
and the circuit is closed, the input (X) turns on.
The input display LED turns on.
Fuse
24 V DC
Fuse
24 V DC
Fuse
L
N
100 to 240 V AC
S/S
0V
24V
*1
X0
X1
X7
*1 Input impedance
In the source input, the input (X) is turned on by connecting 24 V DC [-] with
the [COM] terminal or [S/S] terminal, and connecting a no-voltage contact
or PNP open collector transistor output between the input terminal and 24
V DC to close the circuit.
At this time, the input display LED turns on. For the module having DISP
switch, LED complying with DISP switch turns on.
• Source input wiring
*1
X0
X1
*2
COM
*1 Input impedance
*2 Depending on the module, the [COM] terminal is
[S/S] terminal.
6
Fuse
24 V DC
6 WIRING
123
6.5 Input Wiring