■In-phase
PLC output contacts (*) should be used in an "in-phase" manner.
*
*
*
Transistor output
For output specifications of the CPU module, refer to Page 36 Output Specifications.
For output specifications of the I/O modules, refer to Page 195 Output specifications.
For output specifications of the terminal modules, refer to Page 214 Output specifications.
Sink and source output
Sink output and source output products are available for transistor outputs of the CPU module, I/O modules, and terminal
modules.
■Differences in circuit
•
Sink output [-common]
Output to make load current flow into the output (Y) terminal is
called sink output.
Load
Y
COM
Fuse
DC power supply
A number is entered in the of [COM].
Handling of transistor output
■Output terminal
For the CPU module, output module (extension cable type), input/output module (extension cable type), powered input/output
module and high-speed pulse input/output module, the transistor output type is a 4-point or 8-point common output type.
•
Sink output
Connect each COM (number) terminal to the minus side of
the load power supply.
The COM terminals are not connected internally.
Load
Y0
Y1
DC power
Fuse
supply
COM0
Load
Y4
Y5
DC power
Fuse
supply
COM1
*
•
Source output [+common]
Output to make load current flow out of the output (Y) terminal
is called source output.
Load
Fuse
DC power supply
A number is entered in the of [+V].
•
Source output
Connect +V (number) terminal to the plus side of the load
power supply.
The +V terminals are not connected internally.
Load
DC power
Fuse
Load
DC power
Fuse
Y
+V
Y0
Y1
supply
+V0
Y4
Y5
supply
+V1
6
6 WIRING
137