Mitsubishi Electric MELSEC iQ-F FX6U Hardware User Manual page 72

Table of Contents

Advertisement

4.
Check if expansion to the CPU module is permitted.
• 5 V DC power supply
Capacity of 5 V DC
power supply
CPU module
mA
Ex.
900 mA
• 24 V DC power supply
The value obtained by this calculation (when the value is positive) indicates the remaining capacity of 24 V DC service power
supply, and the capacity can be used for external loads.
Capacity of 24 V DC
power supply
CPU module
mA
400 mA
Ex.
If the calculation result is a negative value, the current consumption exceeds the power supply capacity of the CPU module.
Reconfigure the system, adding powered input/output module or extension power supply modules.
4 SYSTEM CONFIGURATION
70
4.4 Limitation on Current Consumption
Current consumption
Total of current
consumed by extension
module
-
mA
510 mA
Current consumption
Total of current
consumed by extension
module
-
mA
240 mA
Calculation result
=
mA ≥
390 mA
Calculation result
=
mA ≥
160 mA
0 mA
0 mA