4.
Check if expansion to the extension power supply module is permitted.
• 5 V DC power supply
Capacity of 5 V DC
power supply
Extension power
supply module
mA
1200 mA
Ex.
• 24 V DC power supply
Capacity of 24 V DC
power supply
Extension power
supply module
mA
625 mA
Ex.
If the calculation result is a negative value, the current consumption exceeds the power supply capacity of the extension
power supply module.
Reconfigure the system, adding powered input/output module or extension power supply modules.
4 SYSTEM CONFIGURATION
78
4.4 Limitation on Current Consumption
Current consumption
Total of current
consumed by extension
module
-
mA
460 mA
Current consumption
Total of current
consumed by extension
module
-
mA
100 mA
Calculation result
=
mA ≥
740 mA
Calculation result
=
mA ≥
525 mA
0 mA
0 mA