F I R E E X T I N G U I S H I N G S Y S T E M
AUTOMATIC
scale ( Do not use any hand held scales). If weight is below
that shown on the unit nameplate, it must be removed
from service immediately. If leakage is suspected, brush
liquid soap on all points of possible leaks, or submerge
entire unit in clean fresh water and watch carefully for
5 or 10 minutes.
Leaks will appear as tiny bubbles. If leakage is found re-
turn to the factory immediately for repair or replacement.
Remember the two most important requirements to as-
sure full charge and reliability of your Fireboy system are:
1. Visual inspection of the gauge and the actuator to
determine if it has actuated.
2. Weighing to determine the true contents of the agent
in the system.
All models from 75 cubic feet are rechargable. Recharging
is possible only if the unit has leaked out verses losing
agent due to a re.
Should the indicator light fail to come ON when the igni-
tion key is ON, rst check the pressure gauge and actuator
to see if the unit has discharged.If not check the breaker.
Next, using a continuity tester, check the electrical pres-
sure switch on the system bottle itself. Pull the molded
rubber connector o by pulling straight away from the
manifold, and place the probes of the continuity tester
directly on the spade connectors.
should show a closed circuit.
Inspect the pressure gauge
before each outing.
illustration shows the
ready and discharge con-
dition of the actuator. Re-
move and weigh the unit
(minus brackets) every 6
months on an accurate
is pressure switch
e
Next, check the continuity of the entire wiring circuit.
e indicator lamp is an LED (light emitting diode) and
cannot be tested with a continuity tester.
A simple method to test LED'S is to remove the lamp and
touch the red wire to the + terminal and the black wire
to the - terminal of an ordinary 9 volt battery. Should the
indicator lamp be faulty, replacement lamps are available
from Fireboy.
Should the continuity of the pressure switch indicate an
open circuit, the system will have to be returned to the
factory for either replacement or repair.