Table 7.8 - Wiring The Output Relay Terminal Strip - Reliance electric GV3000/SE Hardware Reference, Installation, And Troubleshooting Manual

Bookshelf drive
Hide thumbs Also See for GV3000/SE:
Table of Contents

Advertisement

Terminal
Number
28
Normally-Closed Contact
(Form B)
29
Normally-Closed Contact
Common (Form B)
30
Normally-Open Contact
(Form A)
31
Normally-Open Contact
Common (Form A)
7-14
Table 7.8 – Wiring the Output Relay Terminal Strip
Description
Wiring the Output Status Relays
Parameters/Wiring Connections
Both Form A and Form B contacts are rated for
250 VAC/30 VDC at 5 amps resistive or 2 amps inductive
load.
The following parameter must be set:
P.013: Output Relay Configuration
Note that depending on the setting of parameter P.013, the
relay coil will energize (the normally-open contact will close
and the normally-closed contact will open). Refer to the
GV3000/SE Bookshelf Drive Software Start-Up and
Reference manual for more information.
GV3000/SE AC Bookshelf Drive Hardware Reference, Version 6.06