A-2
Condition
Operating Temperature (Ambient)
Storage Temperature (Ambient)
Transportation Temperature (Ambient)
Table A.3 – Terminal Strip Input Specifications
Signal Type
Speed Reference Input
Digital Inputs (1 - 8)
Table A.4 – Terminal Strip Output Specifications
Signal Type
Analog Output
Table A.2 – Environmental Condition
0° to +40°C (32° to 104°F) coolant air inlet
temperature at heatsink
Derating factor at 45°C ambient: 7.5%
Derating factor at 50°C ambient: 15%
-25°C to +55°C
-25°C to +70°C (+70°C during a maximum
24 hours)
Terminal(s)
12-15
16
17
18
19
20
21
22
23
24
Terminal(s)
10 -11
scaled signal
GV3000/SE AC Bookshelf Drive Hardware Reference, Version 6.06
Specification
Specification
10 V (@ 50K ohm input
impedance or 20 mA)
+24 VDC Isolated Supply
Remote/Local (Default)
Ramp 1/Ramp 2 (Default)
Forward/Reverse (Default)
Function Loss
Run/Jog
Reset
Stop
Start
Specification
0-10 VDC (maximum 4
mA, 2.5K ohm impedance)
or 4-20 mA