2.8 Output Relay Terminal Strip
2.9 Internal Braking Transistor
2.10 Optional Internal AC Mains Filter
2.11 Optional Equipment
2-12
The output relay terminal strip, located on the Power board, provides a set of Form A
and B contacts. These contacts are the under control of the user via programmable
parameters. A Form A or B transition can be used to indicate drive status. The
contacts are rated for 2 amps resistive load at 250 VAC/ 30 VDC. See figure 2.11
An internal braking transistor connects externally mounted, user-supplied braking
resistors to the DC bus and prevents DC bus overvoltage faults. The resistor switches
on during motor regeneration. See chapter 8 for more information.
A built-in line filter limits radio frequency emission to EMC permitted values. It provides
the same function as a line reactor.
An AC Mains Filter is required if the installation must be in compliance with the
European Community Electromagnetic Compatibility Standard. See Appendix C for
more information.
Table 2.2 lists standard GV3000/SE kits and options.
Description
Motor Encoder Cable
ControlNet Network Option Board
InterBus Network Option Board
AutoMax Network Option Board with
762mm (30") of Cable
AutoMax RS-232 Adapter Cable
28
N. C. Relay Contact
29
N. C. Relay Common
30
N. O. Relay Contact
31
N . O . R e l a y C o m m o n
Figure 2.11 – Output Relay Terminal Strip