Terminal
Number
16
+24 VDC Power Supply
17
Digital Input 8
(Default - Remote/Local)
ATTENTION: If a maintained start contact is used when the control source = rE, switching
from local to remote from the terminal strip will cause power to be applied to the motor if
!
the remote start contact is closed. Stay clear of rotating machinery in this case. Failure to
observe this precaution could result in bodily injury.
Wiring the Regulator Board Terminal Strip and the Output Relay Terminal Strip
Table 7.6 - Wiring Signal and Control I/O to the Regulator Board Terminal Strip (Continued)
Description
Wiring a Remote/Local Input
Parameters/Wiring Connections
Current limited for remote input logic use only.
Digital input 8 is control function programmable through
parameter P.007.
The following parameters must be set:
P.000: Control Source (Only active when P.000 = rE)
P.006: Second Menu Password
P.007: Terminal Strip Digital Inputs Configure (Selects and
assigns a control function to digital inputs 6 to 8)
P.008: Terminal Strip Speed Reference Source
(Analog, Motor Operated Potentiometer (MOP), or
Preset Speeds)
Note that based on the settings of parameters P.000, P.007,
P.008, and r.030 if an RMI board is used, the following
parameters can affect digital input 8:
P.023: MOP Accel/Decel Time
P.024: MOP Reset Configuration
P.031 to P.038: Preset Speeds 1-8
Refer to the GV3000/SE Bookshelf Drive Software Start-Up
and Reference manual for additional information.
Terminal 17 On = Local Control
Diagram shows factory setting.
7-9