Meeting Encoder Specifications (Fvc Regulation Only); Encoder Wiring Guidelines; Verifying Power Module Output Current Rating Is Greater Than Motor Full Load Amps - Reliance electric GV3000/SE Hardware Reference, Installation, And Troubleshooting Manual

Bookshelf drive
Hide thumbs Also See for GV3000/SE:
Table of Contents

Advertisement

3.2.4 Meeting Encoder Specifications (FVC Regulation Only)

3.2.4.1 Encoder Wiring Guidelines

3.2.5 Verifying Power Module Output Current Rating Is Greater Than
Planning Before Installing
Table 3.10 – AC Input Fuse Selection Values (Continued)
U.S.
European
Model
Stock
Number
Number
300ER40xx
896.09.11
300ET40xx
896.09.31
430ER40xx
896.11.12
430ET40xx
896.11.32
1
AC line input current (RMS) is dependent on total line impedance.
2
Recommended type of external input fuse:
AC line input: Branch circuit protection fuse, e.g., IEC 269-1/gG, EN 60269-1, VDE 0636/gL, UL Class
J, or equivalent.
DC bus input: Semiconductor protection fuse, 660 V or 750 V, superfast, e.g., A70P500, VDE 0636/aR,
or equivalent.
GV3000/SE drives set up for FVC regulation require an encoder for closed-loop
operation. Refer to table A.5 for specifications. Drives set up for V/Hz or SVC
regulation do not require an encoder for feedback.
Encoder connections are considered signal level wiring and, therefore, must be run
separate from control and power wiring. Reliance Electric recommends 18 AWG
unshielded twisted pair wires with 2-3 twists per inch for applications to a maximum
distance of 303 meters (1000 feet). The recommended Reliance Electric part number
is 417900-207CG; 18 AWG, 6 conductor (3 twisted pairs).
Motor Full Load Amps
Verify that the GV3000/SE output current rating is greater than the motor's full load
current (amps). Table 2.1 lists the output current values.
AC Input
1
Choke
Current
No
38 A
Yes
32 A
No
53 A
Yes
47 A
2
External Fuse
Nominal
Maximum
50 A
50 A
63 A
63 A
3-9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents