Reliance electric GV3000/SE Hardware Reference, Installation, And Troubleshooting Manual page 50

Bookshelf drive
Hide thumbs Also See for GV3000/SE:
Table of Contents

Advertisement

6-2
ATTENTION: Do not route signal and control wiring with power wiring in
the same conduit. This can cause interference with drive operation.
!
Failure to observe these precautions could result in damage to, or
destruction of, the equipment
ATTENTION: Unused wires in conduit must be grounded at both ends
to avoid a possible shock hazard caused by induced voltages. Also, if a
drive sharing a conduit is being serviced or installed, all drives using this
conduit should be disabled to eliminate the possible shock hazard from
cross-coupled motor leads. Failure to observe these precautions could
result in bodily injury.
Step 2. Connect the three-phase AC output power motor leads to terminals U, V, and
W.
Step 3. Tighten the three-phase AC output power terminals to 1.4 Nm (12 in-lb).
GV3000/SE AC Bookshelf Drive Hardware Reference, Version 6.06