Input: 240 / 480 VAC, 60 Hz, 150/75 AAC
400 VAC, 50 Hz, /50 AAC
(Note: The above current levels are based on the 30 minute duty cycle. To estimate the current draw on
the facility power at different duty cycles, multiply the above currents by the ratio of the output currents.
Ex.: An HC-75C will draw approximately 7.5 times the above current at the 1 second duty cycle.)
Output:
1 Second ON /
DUTY CYCLE
2 Minutes OFF
HC-12C
HC-20C
HC-40C
HC-75C
*Note: The HC-C Controller will impose a shutdown and a 5-minute off time if one of the above limits is exceeded.
1 Second ON /
DUTY CYCLE
2 Minutes OFF
HC-12C
HC-20C
HC-40C
HC-75C
*Note: The HC-C Controller will impose a shutdown and a 5-minute off time if one of the above limits is exceeded.
Connection /
Series / 60Hz
Frequency
HC-12C
HC-20C
HC-40C
HC-75C
*Note: Output voltage will vary with input. Values given are at nominal.
HC-20C
SECTION 1: SPECIFICATIONS
OUTPUT CURRENT SPECIFICATIONS
(PARALLEL CONNECTION)
1 Minute ON /
10 Minutes OFF
12,000 A
20,000 A
40,000 A
75,000 A
OUTPUT CURRENT SPECIFICATIONS
(SERIES CONNECTION)
1 Minute ON /
10 Minutes OFF
6,000 A
10,000 A
20,000 A
37,500 A
OUTPUT VOLTAGE SPECIFICATIONS
(OPEN CIRCUIT)
Parallel / 60Hz
15 V
7.5 V
20 V
10 V
24 V
12 V
32 V
16 V
30 Minute ON /
30 Minutes OFF
2,500 A
1,700 A
4,500 A
3,000 A
9,000 A
6,000 A
15,000 A
10,000 A
30 Minute ON /
30 Minutes OFF
1,250 A
850 A
2,250 A
1,500 A
4,500 A
3,000 A
7,500 A
5,000 A
Series / 50Hz
12.5 V
16.6V
20 V
26.6 V
Continuous
1,200 A
2,000 A
4,000 A
7,500 A
Continuous
600 A
1,000 A
2,000 A
3,750 A
Number of
Parallel / 50Hz
Taps
6.25 V
8.3 V
10 V
13.3 V
1-1
3
4
6
8