Fault logger mode

The Fault logger mode is used for viewing faults. You can:
view the drive fault history of maximum ten faults (after a
power off, only the three latest faults are kept in the memory)
see the details of the three latest faults (after a power off, the
details of only the most recent fault is kept in the memory)
read the help text for the fault.
To view the faults, follow the steps below. For more information
on faults, see section
1
Press MENU to go to the
main menu.
2
Scroll to FAULT LOGGER
with the UP/DOWN keys
and press ENTER to go to
the Fault logger mode.
3
The display shows the fault
log starting with the latest
fault. The number on the
row is the fault code (see
the listing on page 371).
To see the details of a fault,
select it with the UP/DOWN
keys and press DETAIL.
4
Scroll the details with the
UP/DOWN keys.
To show the help text,
press DIAG. Scroll the help
text with the UP/DOWN
keys. After reading the
help, press OK to go back
to the previous display.
Press EXIT three times to
return to the main menu.
92
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
ACH550-01 User's Manual
Correcting faults
on page 371.
Start-up and control panel
OFF
0.
0 Hz
0.
0 A
0.
0 %
00:00
MENU
OFF
MAIN MENU
ASSISTANTS
CHANGED PAR
FAULT LOGGER
EXIT
00:00
ENTER
OFF
FAULT LOGGER
10:
PANEL LOSS
06.02.06 14:07:12
14:
EXT FAULT 1
EXIT
00:00
DETAIL
OFF
PANEL LOSS
FAULT
10
FAULT TIME 1
14:07:12
FAULT TIME 2
EXIT
00:00
DIAG
OFF
DIAGNOSTIC
Check: Comm lines
and connections,
Parameter 3002,
parameters in groups
10 and 11.
EXIT
00:00
0.0Hz
4
1