ACH550-01 User's Manual
Code Description
4027 PID 1 PARAM SET
Process PID (PID1) has two separate sets of parameters, PID set 1 and
PID set 2.
PID
• PID set 1 uses parameters 4001...4026.
• PID set 2 uses parameters 4101...4126.
0 =
1 – PID set 1 (parameters 4001...4026) is active.
SET
1 =
1 – Defines digital input
DI
• Activating the digital input selects PID set 2.
• De-activating the digital input selects PID set 1.
2...6 =
2...
DI
DI
set selection.
• See
1 above.
DI
7 =
2 – PID set 2 (parameters 4101...4126) is active.
SET
8...11 =
TIMER
selection (Timer de-activated = PID set 1; Timer activated = PID set
2)
• See parameter
-1 =
1(
) – Defines an inverted digital input
DI
INV
set selection.
• Activating the digital input selects PID set 1.
• De-activating the digital input selects PID set 2.
-2...-6 =
2(
DI
INV
as the control for PID set selection.
• See
1(
DI
INV
For 2-
selections (12...14), the drive first calculates the difference
ZONE
between PID1 set 1 setpoint and feedback (deviation) as well as the
difference between PID1 set 2 setpoint and feedback (deviation).
12 = 2-
ZONE MIN
PID1 set 1 or PID1 set 2) which has a larger deviation.
• A positive deviation (a setpoint higher than the feedback) is always
larger than a negative deviation. This keeps feedback values at or
above the setpoint.
• Controller does not react to the situation of feedback above setpoint
if another zone's feedback is closer to its setpoint.
13 = 2-
ZONE MAX
PID1 set 1 or PID1 set 2) which has a smaller deviation.
• A negative deviation (a setpoint lower than the feedback) is always
smaller than a positive deviation. This keeps feedback values at or
below the setpoint.
• Controller does not react to the situation of feedback below setpoint
if another zone's feedback is closer to its setpoint.
14 = 2-
ZONE AVE
and uses it to control zone 1. Therefore one feedback is kept above
its setpoint and another is kept as much below its setpoint.
Parameter listing and descriptions
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
1
defines which set is selected.
PARAM SET
1 as the control for PID set selection.
DI
6 – Defines digital input
1...4 – Defines the timer as the control for the PID set
Group 36: TIMED
)...
6(
) – Defines an inverted digital input
DI
INV
) above.
– The drive will control the zone (and select the set,
– The drive will control the zone (and select the set,
– The drive calculates the average of the deviations,
Range
-6...11
2...
6 as the control for PID
DI
DI
FUNCTIONS.
1 as the control for PID
DI
2...
6
DI
DI
289