ABB ACH550-01 User Manual page 206

Hide thumbs Also See for ACH550-01:
Table of Contents

Advertisement

ACH550-01 User's Manual
Group 14: RELAY OUTPUTS
This group defines the condition that activates each of the relay
outputs.
Code Description
1401 RELAY OUTPUT 1
Defines the event or condition that activates relay 1 – what relay output
1 means.
0 =
– Relay is not used and is de-energised.
NOT SEL
1 =
– Energise the relay when the drive is ready to function.
READY
Requires:
• Run enable signal is present.
• No faults exist.
• Supply voltage is within range.
• Emergency Stop command is not on.
2 =
– Energise the relay when the drive is running.
RUN
3 =
(-1) – Energise the relay when power is applied. De-energise
FAULT
when a fault occurs.
4 =
– Energise the relay when a fault is active.
FAULT
5 =
– Energise the relay when an alarm is active.
ALARM
6 =
REVERSED
direction.
7 =
STARTED
command (even if Run enable signal is not present). De-energise the
relay when the drive receives a stop command or a fault occurs.
8=
1
SUPRV
OVER
parameter (3201) exceeds the limit (3203).
• See
Group 32:
9 =
1
SUPRV
UNDER
parameter (3201) drops below the limit (3202).
• See
Group 32:
10 =
2
SUPRV
parameter (3204) exceeds the limit (3206).
• See
Group 32:
11 =
2
SUPRV
parameter (3204) drops below the limit (3205).
• See
Group 32:
12 =
3
SUPRV
parameter (3207) exceeds the limit (3209).
• See
Group 32:
13 =
3
SUPRV
parameter (3207) drops below the limit (3208).
• See
Group 32:
Parameter listing and descriptions
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
– Energise the relay when the motor rotates in reverse
– Energise the relay when the drive receives a start
– Energise the relay when the first supervised
SUPERVISION.
– Energise the relay when the first supervised
SUPERVISION.
– Energise the relay when the second supervised
OVER
SUPERVISION.
– Energise the relay when the second supervised
UNDER
SUPERVISION.
– Energise the relay when the third supervised
OVER
SUPERVISION.
– Energise the relay when the third supervised
UNDER
SUPERVISION.
Range
0...47
201

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ach550

Table of Contents