Code Description
5 =
(0) – Sensor configuration uses a thermistor.
THERM
• Motor thermal protection is activated through a digital input. Connect
either a normally closed thermistor relay or a PTC sensor to a digital
input.
• When the digital input is '0', the motor is overheated.
• See the connection figures on page 262.
• The table below and the graph on page
requirements for a PTC sensor connected between 24 V and digital
input as a function of the motor operating temperature.
Temperature
Normal
Excessive
6 =
(1) – Sensor configuration uses a thermistor.
THERM
• Motor thermal protection is activated through a digital input. Connect
a normally open thermistor relay to a digital input.
• When the digital input is '1', the motor is overheated.
• See the connection figures on page 262.
3502 INPUT SELECTION
Defines the input used for the temperature sensor.
1 =
1 – PT100 and PTC
AI
2 =
2 – PT100 and PTC
AI
3...8 =
1...
DI
3503 ALARM LIMIT
Defines the alarm limit for
the motor temperature measurement.
• At motor temperatures above this limit, the drive displays an alarm
(2010,
MOTOR TEMP
For thermistors or PTC connected to digital input:
0 – De-activated.
1 – Activated.
3504 FAULT LIMIT
Defines the fault limit for
the motor temperature measurement.
• At motor temperatures above this limit, the drive displays a fault (9,
MOT OVERTEMP
For thermistors or PTC connected to digital input:
0 – De-activated.
1 – Activated.
264
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Resistance
< 3 kohm
> 28 kohm
6 – Thermistor and PTC.
DI
)
) and stops the drive.
ACH550-01 User's Manual
Range
263
show the resistance
1...8
-10...200 °C
0...5000 ohm
0...1
-10...200 °C
0...5000 ohm
0...1
Parameter listing and descriptions