ACH550-01 User's Manual
1...10 kohm
1
Not available if PID is activated
2
Disable/enable with parameter 1608
3
The sensor for AI2 is powered externally (not shown in the figure). See the manufacturer's
instructions. To use sensors supplied by the drive auxiliary voltage output, see page 124.
Note: The drive starts only if possible protection functions (Run enable or Start enable 1 and
2) are activated from I/O or disabled with parameters.
Application macros and wiring
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
HVAC default
for typical BMS applications
1
SCR
Signal cable shield (screen)
2
AI1
External reference 1: 0(2)...10 V or 0(4)...20 mA
3 AGND Analogue input circuit common
4
10V
Reference voltage +10 V DC
5
AI2
Actual signal 1: 0(2)...10 V or 0(4)...20 mA
6 AGND Analogue input circuit common
7
AO1
Output frequency: 0(4)...20 mA
8
AO2
Output current: 0(4)...20 mA
9 AGND Analogue output circuit common
10
24V
Auxiliary voltage output +24 V DC
11
GND
Common for DI return signals
12 DCOM Digital input common for all
13
DI1
Start/Stop: Activation starts the drive
14
DI2
Not used
15
DI3
Constant speed 1 (par. 1202)
16
DI4
Start enable 1: Deactivation stops the drive
17
DI5
Not used
18
DI6
Not used
19 RO1C
Relay output 1 (par. 1401)
20 RO1A
Default operation
Ready => 19 connected to 21
21 RO1B
22 RO2C
Relay output 2 (par. 1402)
23 RO2A
Default operation
Running => 22 connected to 24
24 RO2B
25 RO3C
Relay output 3 (par. 1403)
26 RO3A
Default operation
Fault (-1) => 25 connected to 27
27 RO3B
3
1
2
97