ABB ACH550-01 User Manual page 177

Hide thumbs Also See for ACH550-01:
Table of Contents

Advertisement

Group 01: OPERATING DATA
This group contains drive operating data, including actual
signals. The drive sets the values for actual signals, based on
measurements or calculations. You cannot set these values.
Code Description
0101 SPEED & DIR
Calculated signed speed of the motor (rpm). The absolute value of 0101
&
SPEED
DIR
• The value of 0101
forward direction.
• The value of 0101
reverse direction.
0102 SPEED
Calculated speed of the motor (rpm)
0103 OUTPUT FREQ
Frequency (Hz) applied to the motor. (Also shown by default in the
OUTPUT display.)
0104 CURRENT
Motor current, as measured by the ACH550. (Also shown by default in
the OUTPUT display.)
0105 TORQUE
Output torque. Calculated value of torque on motor shaft in % of the
motor nominal torque.
0106 POWER
Measured motor power in kW
0107 DC BUS VOLTAGE
DC bus voltage in V DC, as measured by the ACH550
0109 OUTPUT VOLTAGE
Voltage applied to the motor
0110 DRIVE TEMP
Temperature of the drive heatsink in Celsius
0111 EXTERNAL REF 1
External reference,
9904
0112 EXTERNAL REF 2
External reference,
172
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
is the same as the value of 0102 speed.
&
SPEED
DIR
&
SPEED
DIR
, in rpm or Hz – units determined by parameter
1
REF
2, in %
REF
ACH550-01 User's Manual
Range
-30000...30000 rpm
is positive if the motor runs in the
is negative if the motor runs in the
0...30000 rpm
0.0...500.0 Hz
type dependent
-200...200%
type dependent
0...2.5 · V
0...2.0 · V
0...150 °C
0...300000 rpm/
0...500 Hz
0...100%
(0...600% for torque)
Parameter listing and descriptions
dN
dN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ach550

Table of Contents