Code Description
8120 INTERLOCKS
Defines operation of the Interlock function. When the Interlock function
is enabled:
• An interlock is active when its command signal is absent.
• An interlock is inactive when its command signal is present.
• The ACH550 will not start if a start command occurs when the speed
regulated motor's interlock is active – the control panel displays an
alarm (2015,
Wire each Interlock circuit as follows:
• Wire a contact of the motor's On/Off switch to the Interlock circuit –
the drive's PFA logic can then recognise that the motor is switched off
and start the next available motor.
• Wire a contact of the motor thermal relay (or other protective device in
the motor circuit) to the Interlock input – the drive's PFA logic can then
recognise that a motor fault is activated and stop the motor.
0 =
– Disables the Interlock function. All digital inputs are
NOT SEL
available for other purposes.
• Requires 8118
must be disabled if Interlock function is disabled.)
Parameter listing and descriptions
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
).
PFA I LOCK
AUTOCHNG INTERV
Range
0...6
= 0.0 (The Autochange function