Group 20: LIMITS
This group defines minimum and maximum limits to be followed
in driving the motor – speed, frequency, current, torque, etc.
Code Description
2001 MINIMUM SPEED
Defines the minimum speed (rpm) allowed.
• A positive (or zero) minimum speed value defines two ranges, one
positive and one negative.
• A negative minimum speed value defines one speed range.
• See the figure.
-(P 2001)
-(P 2002)
2002 MAXIMUM SPEED
Defines the maximum speed (rpm) allowed.
2003 MAX CURRENT
Defines the maximum output current (A) supplied by the drive to the
motor.
Parameter listing and descriptions
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Speed
P 2002
Speed range allowed
0
P 2001
Speed
P 2002
Speed range allowed
P 2001
0
Speed range allowed
Range
-30000...30000 rpm
2001 value is < 0
Time
2001 value is > 0
Time
0...30000 rpm
depends on drive type