Fcontrol
FXDM
Frequency inverter with integrated sine lter for 3 ~ fans
Operating Instructions
Keep for reference!
Software version: D1333A from Version 2.37
L-BAL-E072-GB 1642 Index 008
Part.-No.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FXDM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ZIEHL-ABEGG FXDM

  • Page 1 Fcontrol FXDM Frequency inverter with integrated sine lter for 3 ~ fans Operating Instructions Keep for reference! Software version: D1333A from Version 2.37 L-BAL-E072-GB 1642 Index 008 Part.-No.
  • Page 2: Table Of Contents

    Operating Instructions Fcontrol – model series FXDM Content General notes .............
  • Page 3 Operating Instructions Fcontrol – model series FXDM 5.10 Voltage supply for external devices (+24V, GND) ......
  • Page 4 Operating Instructions Fcontrol – model series FXDM Controller Setup ............
  • Page 5 Operating Instructions Fcontrol – model series FXDM Diagnostics menu ............
  • Page 6: General Notes

    We do not accept any liability for possible errors or omissions in the information contained in data, illustrations or drawings provided. ZIEHL-ABEGG SE is not liable for damage due to misuse, incorrect use, improper use or as a consequence of unauthorized repairs or modifications.
  • Page 7: Product Safety

    Operating Instructions Fcontrol – model series FXDM Safety instructions Attention! General hazardous area. Death or severe injury or significant property damage can occur if the corresponding precautions are not taken! Danger due to electric current Danger by dangerous, electric voltage! Death or severe injury can occur if the corresponding...
  • Page 8: Work On The Device

    Use only genuine spare parts / genuine wearing parts / genuine accessories from ZIEHL-ABEGG.Th- ese parts were specifically designed for the device. There is no guarantee that parts from non-original sources are designed and manufactured in correspondence with load and safety requirements.
  • Page 9: Employment Of External Personnel

    Operating Instructions Fcontrol – model series FXDM Product overview Employment of external personnel Maintenance and service work are frequently carried out by external employees who often do not recognize the specific situations and the thus resulting dangers.These persons must be comprehen- sively informed about the hazards in their area of activity.
  • Page 10: Transport

    Operating Instructions Fcontrol – model series FXDM Mounting Transport • The device is packed ex factory to suit the transport method previously agreed. • Always use the original packaging materials when transporting the device. • Avoid shocks and impacts to the device during the transport.
  • Page 11: Fastening The Device

    Operating Instructions Fcontrol – model series FXDM Mounting Fastening the device The type of fastening and the number of fastening points are dependent on the housing design. All the fastening points available must be used for safe fastening. Proceed as follows: Type FXDM2.5AM...
  • Page 12 Operating Instructions Fcontrol – model series FXDM Mounting Type FXDM5...18 (FXDM22) Fastening at 4 points GM00005A_M 15.12.2015 Drill fastening points “1” - “4”. " " Fasten device with screws. Type FXDM32...50 (IP54 / IP65) Fastening at 8 points GM00002A_M 15.12.2015 "...
  • Page 13: Cable Inlet

    Operating Instructions Fcontrol – model series FXDM Mounting Type FXDM32...50 (IP20) Fastening at 4 points GM00001A_M 15.12.2015 Drill 4 fastening points. " Screw in screws “1” - “4” up to a distance of approx. 5 mm and mount the device.
  • Page 14: Outdoor Installation

    Operating Instructions Fcontrol – model series FXDM Electrical installation Sheet metal housing IP54 IP20 1 Inlet mains connection (32 mm) 1 Inlet mains connection (40 mm) 2 Inlet motor connection (32 mm) 2 Inlet motor connection (40 mm) 3 Ridges for connecting the control cables...
  • Page 15: Terminal Compartment

    Operating Instructions Fcontrol – model series FXDM Electrical installation authorized persons using a key or special tool. • Operating the device with the housing cover removed is prohibited because energized, exposed parts are present inside the device. Disregarding this regulation can lead to severe personal injury.
  • Page 16: Emc-Compatible Installation

    Operating Instructions Fcontrol – model series FXDM Electrical installation Possible cross sections of terminals for control section For all types flexible rigid Modulation 0,25 - 1,5 mm 0,25 - 1,5 mm Indication relays 0,08 - 2,5 mm 0,08 - 2,5 mm...
  • Page 17: Required Quality Attributes For The Mains Voltage

    Operating Instructions Fcontrol – model series FXDM Electrical installation 5.4.2 Required quality attributes for the mains voltage Danger due to electric current The mains voltage must comply with the EN 50160 quality characteristics and the defined standard voltages in IEC 60038! 5.4.3...
  • Page 18: Signal Connection Or Sensor Connection To Analog Inputs (Analog In 1, Analog In 2)

    Operating Instructions Fcontrol – model series FXDM Electrical installation Display during motor fault Motor fault Possibilities for re-starting after the drive has cooled down terminals “TB/TP” bridged by: • By switching the mains voltage off and then on again. •...
  • Page 19: Connection Of External Terminal Type Axg-1A(E)

    Operating Instructions Fcontrol – model series FXDM Electrical installation 5.12 Connection of external Terminal type AXG-1A(E) An external terminal is required for starting-up and setting-up versions that do not have an integrated terminal. • Model AXG-1A, Part-No. 349034 for wall mounting •...
  • Page 20 Operating Instructions Fcontrol – model series FXDM Electrical installation general example for MODBUS device connection The data line must be connected from one device to the next. No other type of wiring is allowed! Always use only two wires of one lead (twisted pair) for the connection.
  • Page 21: Lon Bus System Is Possible Via Add-On Module

    Operating Instructions Fcontrol – model series FXDM Electrical installation Default interface parameter Baudrate 19200 Bits Parity Even (None, exception of devices agriculture) Stop bits Handshake none Information If any matters are unclear, please contact our V-STE support department for control systems - ventilation technology.
  • Page 22: Manual Bypass-Switch Type S-D-25 And S-D-50

    Operating Instructions Fcontrol – model series FXDM Electrical installation 5.18 Manual Bypass-Switch type S-D-25 and S-D-50 As accessories are manual main switches with bypass function available. By switching OFF Frequency inverters necessary waiting period before renewed switching on amounts minimum 90 seconds! Switch position •...
  • Page 23: Controls And Menu

    Operating Instructions Fcontrol – model series FXDM Controls and Menu 6 Controls and Menu Multipurpose LC display and keyboard 2 3 4 5 6 7 8 9 19.02.2014 v_display_erklaerung_fcontrol.vsd 1. Numeric display 5 digit Program key and open menu 2. Moon-Symbol for set point 2 Menu selection, reduce value ▼...
  • Page 24: Menu Operation

    Operating Instructions Fcontrol – model series FXDM Controls and Menu Menu operation Display after turning on the voltage supply. description for menu language English = “GB” (delivery status). Switch over between “Start” and *Actual value with Escape Example for mode 1.01...
  • Page 25: Menu Structure

    Operating Instructions Fcontrol – model series FXDM Controls and Menu Menu structure PIN 0010 STOP ← ← ← ← User Service → → → → ▼ ▼ ▼ ▼ ▲ ▲ ▲ ▲ Start Info Setting Events Base setup P↓ ↑ ESC P↓...
  • Page 26: Base Setup

    Operating Instructions Fcontrol – model series FXDM Base setup 7 Base setup Jumper for the input signal Jumper position factory setting for 0 - 10 V signal. For temperature sensors (TF..) or sensors with 4 - 20 mA bring the internal jumper for the external signal in the correct position.
  • Page 27: Select Operation Mode

    Operating Instructions Fcontrol – model series FXDM Base setup Select operation mode Information Simple installation is possible through the selection of the preprogrammed mode of operation. This determines the basic function of the device; factory setting 1.01 = Speed controller (activation via 0 - 10 V signal).
  • Page 28: Start-Up

    Operating Instructions Fcontrol – model series FXDM Start-up 8 Start-up Prerequisites for commissioning Attention! 1. You must mount and connect the device in accordance with the operating instructions. 2. Double check that all connections are correct. 3. The mains voltage must match the information on the rating plate.
  • Page 29: Menu Mode 1.01

    Operating Instructions Fcontrol – model series FXDM Start-up Switch Motor to ON in menu group “Start” ▲ Menu Mode 1.01 Base Controller Motor Start Info Setting Events IO Setup Limits Diagnostic setup Setup Setup 50.0 Hz 8.0 A 1.01 0.0 Hz...
  • Page 30: Programming

    Operating Instructions Fcontrol – model series FXDM Programming 9 Programming Speed controller 1.01 1.02 9.1.1 Base setup 1.01 Base setup Base setup Mode Factory setting Mode: 1.01 Mode E1 Analog In Selection: 0 - 20 mA, 4 - 20 mA, Bus (Inverting...
  • Page 31: Touch Function Via External Signal In Mode 1.01

    Operating Instructions Fcontrol – model series FXDM Programming Diagram setting signal and output frequency [Hz] n-min 10 Hz n-max. = 50 Hz n-min 20 Hz n-max. = 45 Hz n-min OFF n-max. = 50 Hz = 5 Hz = 6 Hz Analog In 1 0...10 V...
  • Page 32 Operating Instructions Fcontrol – model series FXDM Programming Functional description Increase output frequency In order to gradually increase the output frequency, the signal at input “E1” is switched on via contact “C1”. The signal must be higher than set for “E1 Max.” (i.e. over 8 V). The output frequency is now increased depending on the duration of the signal applied and the increment setting “Touch function.-...
  • Page 33: Base Setup 1.02

    Operating Instructions Fcontrol – model series FXDM Programming 9.1.4 Base setup 1.02 Menu group “Base setup” Base setup Base setup Mode Mode selection: 1.02 Mode Number steps Selection: 0, 1, 2, 3, 4, 5 Factory setting: 0 Number steps: 0 In the factory setting “0”...
  • Page 34 Operating Instructions Fcontrol – model series FXDM Programming Menu group “setting” (only when needed) Setting Setting “Base setup”) Setting direct (at Number steps: 0 If the setting is to be made during operation directly with the ▼ + ▲ keys, no setting is...
  • Page 35: Setting In Operation 1.02

    Operating Instructions Fcontrol – model series FXDM Programming 9.1.5 Setting in operation 1.02 After installation is completed, only the “Setting direct” or “Setting Step” setting is visible in the “Info” menu group. All other menus are protected by a PIN.
  • Page 36: Temperature Control 2.01

    Operating Instructions Fcontrol – model series FXDM Programming Temperature control 2.01 2.05 9.2.1 Basic setting 2.01 2.05 Base setup Base setup Mode Mode selection e.g. 2.01 Mode E1 Analog In In all group 2 operating modes (2.01, 2.02, 2.03, ..) “E1 analogue In”...
  • Page 37: Settings For Operation Modes 2.01

    Operating Instructions Fcontrol – model series FXDM Programming 9.2.2 Settings for operation modes 2.01 2.05 2.01 Temperature control simple Temperature control depending on outdoor temperature (Special function: Sensor connection at “E2”, 2.02 display and setting under “E1”). 2.03 Temperature control with pre-programmed additional functions (heating, shutter, temperature monitoring).
  • Page 38: Functional Diagrams Temperature Control

    Operating Instructions Fcontrol – model series FXDM Programming 9.2.3 Functional diagrams temperature control Example 1: Temperature control in factory setting “Cooling function” (Idealized principle diagram) 100 % Min. 0 % Max. = 100 % Min. 35 % Max. = 85 % 50 % Min.
  • Page 39: Additional For Mode

    Operating Instructions Fcontrol – model series FXDM Programming 9.2.4 Additional for mode 2.03 : Signal output 0 - 10 V The 0 - 10 V output signal can, e.g., be used for triggering a shutter or heating. Offset AnalogOut The target value for this output is the target value (Setpoint) for the ventilation “offset”...
  • Page 40: For Mode 2.03 : Relay Output For Heating Or Cooling

    Operating Instructions Fcontrol – model series FXDM Programming 9.2.5 For mode 2.03 : Relay output for Heating or Cooling OffsetDigitalOut Offset Digital Out = Offset for relay output (“K2” is pre-programmed by the factory). The relay operating point deviates by the adjusted offset of the Setpoint of the ventila- OffsetDigitalOut tion (if relay “K2”...
  • Page 41: Relay Output For Temperature Monitoring

    Operating Instructions Fcontrol – model series FXDM Programming 9.2.6 For mode 2.03 Relay output for temperature monitoring If the set value for the “minimum alarm” is not reached or the set value for the “maximum alarm” is exceeded, a message is generated via the alarm symbol in the display. In addition, „Lmt E1 min“ is displayed alternately with the actual value for the minimum alarm and Lmt E1 max for the „Maximum...
  • Page 42: Pressure Control For Condensers Refrigeration 3.01

    Operating Instructions Fcontrol – model series FXDM Programming Pressure control for condensers refrigeration 3.01 3.04 9.3.1 Base setup 3.01 3.04 Base setup Base setup Mode Mode selection e.g. 3.01 Mode E1 Analog In For all Modes in Group 3 ( 3.01...
  • Page 43: Setting For Operation Modes 3.01

    Operating Instructions Fcontrol – model series FXDM Programming 9.3.2 Setting for operation modes 3.01 3.04 3.01 Pressure control condensers, setting Setpoint in bar Pressure control for condensers with input for refrigerant, Setpoint in °C 3.02 3.03 Two sensors for dual circuit condenser. Automatic regulation to the highest pressure (selection amplifier integrated) operation display: “Control value”, Setpoint in bar...
  • Page 44: Functional Diagrams Pressure Control Condensers

    Operating Instructions Fcontrol – model series FXDM Programming 9.3.3 Functional diagrams pressure control condensers Functional diagram for Mode 3.01 3.03 (Idealized principle diagram) 100 % Min. 0 % Max. = 100 % 50 % Min. 17 bar 5 bar 12 bar 09.05.2007...
  • Page 45: Pressure Control Airconditioning 4.01

    Operating Instructions Fcontrol – model series FXDM Programming Pressure control airconditioning 4.01 4.03 9.4.1 Base setup 4.01 4.03 Base setup Base setup Mode Mode selection e.g. 4.01 Mode E1 Analog In , ..) “E1 Analog In” factory setting In all group 2 operating modes 4 ( 4.01...
  • Page 46: Setting For Operation Modes 4.01

    Operating Instructions Fcontrol – model series FXDM Programming 9.4.2 Setting for operation modes 4.01 4.03 • 4.01 pressure control, setpoint in Pa • 4.02 4.03 Pressure control for ventilation systems setpoint depending on outdoor temper- ature Setting Setting Setpoint1 Setting range: in measuring range of sensor...
  • Page 47: Volume Control 5.01

    Operating Instructions Fcontrol – model series FXDM Programming Additional menu item for mode 4.02 4.03 with outside-temperature dependent target- setpoint. Outside-temperature dependent target-setpoint An outside temperature compensation can be activated (sensor connection “E2” = “Analog In [Pa] 2”) when being operated as a pressure regula- tion device.
  • Page 48: Setting For Operation Modes 5.01

    Operating Instructions Fcontrol – model series FXDM Programming E1 Offset Sensor calibration with calibrated comparison device E1 Offset E2 Function (only for special applications) • “Setpoint External setpoint = Function by external signal (0 - 10 V) instead of 1”...
  • Page 49: Air Velocity Control 6.01

    Operating Instructions Fcontrol – model series FXDM Programming Additional menu item for mode 5.02 with outside-temperature dependent target-setpoint Outside-temperature dependent target-setpoint An outside temperature compensation can be activated (sensor connection “E2” to “Analog In Sollwert 1 2”) when being operated as a air volume regu- lation device.
  • Page 50: Settings For Operation Modes 6.01

    Operating Instructions Fcontrol – model series FXDM Programming E2 Function (only for special applications) • “Setpoint External setpoint = Function by external signal (0 - 10 V) instead of 1” . 0 - 10 V 0 - 100 % sensor measuring range.
  • Page 51: Menu Group Start

    Operating Instructions Fcontrol – model series FXDM Programming Menu group Start Start Start Motor (Menu dependent on device type available) In this menu point the modulation for the motor can be switched on and off (ON / OFF). Factory setting to , this prevents the system from inadvertently starting up before configuration is complete.
  • Page 52: Menu Group Info

    Operating Instructions Fcontrol – model series FXDM Programming Menu group Info Menu group Info Info Info for mode speed controller 1.01 Inverter output frequency. Frequency Display of motor current (Metering precision approx. +/-10%) Motor current Input power display (display available depending on the software version)
  • Page 53: Controller Setup

    Operating Instructions Fcontrol – model series FXDM Programming Output power display (display available depending on the software version) Output power Momentarily status for minimum speed cut off “ON” = switch off, if Setpoint (+/- “Min. speed cut off”) is reached.
  • Page 54: Sensor Alarm On / Off

    Operating Instructions Fcontrol – model series FXDM Programming 9.9.4 Sensor Alarm ON / OFF Function only in controller mode ( 2.01 For “E1 Analog In” and if activated for sensor 2 “E2 Analog In”. In case of an interruption or short-circuit in the sensor conductor, or in case of measured values that lie outside of the device’s measurement range, a time-delayed fault indication takes place.
  • Page 55: Minimum Speed Cut Off

    Operating Instructions Fcontrol – model series FXDM Programming 9.9.6 Minimum speed cut off This function is primarily significant for installation of the device as a pure P Controller in refrigeration and air-conditioning technology. For operation mode speed controller 1.01 without function! Min.
  • Page 56: Control Group 2/3/4 Via Relais

    Operating Instructions Fcontrol – model series FXDM Programming Example group 2 via 0 -10 V Fout Standard Fout @ Analog Out = 5A G2 ON = 50 % Controller Master 0...100 % Analog Analog Signal Analog Out = 5A 0 – 10 V...
  • Page 57 Operating Instructions Fcontrol – model series FXDM Programming Group 4 ON value Switch-on value for Group4 Setting range: 0 - 100 % Group 4 ON value Factory setting: 85 % * OFF Value Group4 Switch-off value for group4 Setting range: 0 - 100 %...
  • Page 58: Reverse Action Of The Control Function

    Operating Instructions Fcontrol – model series FXDM Programming 9.9.8 Reverse action of the control function For the effect of the regulation there are two functions: • “Val > Set = n+” increasing Fanlevel for increasing actual value over Setpoint. Val>Set=n+ •...
  • Page 59: Modbus Communication Watchdog

    Operating Instructions Fcontrol – model series FXDM Programming D-component More “D-component” causes more stability by a clean actual value signal with shorter correction times By a actual value signal with a superposition should be done to attitude without “D- component” → 0 % Setting range: 0 - 200 % value smaller = less “D-component”...
  • Page 60: Io Setup

    Operating Instructions Fcontrol – model series FXDM Programming 9.10 IO Setup 9.10.1 Analog-Output “A” The analog outputs 0 - 10 V can be allocated with various functions. Terminals “A” - “GND” = Analog Out (I 10 mA) A Function With the attitudes “A min” and “A max” the characteristic of the output voltage can be adapted.
  • Page 61: Digital Inputs "D1" / "D2

    Operating Instructions Fcontrol – model series FXDM Programming 9.10.2 Digital inputs “D1” / “D2” 9.10.2.1 Menu overview The digital inputs Digital In 1 (D1) and Digital In 2 (D2) can be allocated with various functions. Activation via floating contacts (a low voltage of approx. 24 V DC is connected).
  • Page 62: External Fault Function | 2D

    Operating Instructions Fcontrol – model series FXDM Programming Digital IN 1 Digital IN 1 STOP Display for switch OFF • “ON” Controller for closed contact (fac- tory setting). • “OFF” Controller with opened contact When inverting in reverse i.e. equipment 10.05.2007...
  • Page 63: Switch Over Input Signal "E1" / "E2", Function

    Operating Instructions Fcontrol – model series FXDM Programming - - - - - Controller n = 0- 80 % n = 0- 100 % D1 D1 10.05.2007 v_3d_limit.vsd 1 Setting “Limit” (depending on device type in: %, Hz, rpm) 9.10.2.5 Switch over Input signal “E1”...
  • Page 64: Intern / Extern Function | 6D

    Operating Instructions Fcontrol – model series FXDM Programming • “D1 Inverting” “OFF” “Setpoint1” “Setpoint2” 18 °C at opened contact / - - - - - 25 °C at closed contact. Controller n = 0 – 100 % • “D1 Inverting”...
  • Page 65: Reverse Action Of Control Function

    Operating Instructions Fcontrol – model series FXDM Programming • “D1 Inverting” “OFF” Automatic control at opened contact / manual operation at closed contact. - - - - - - - - - - • “D1 Inverting” “ON” : Automatic control at closed contact / manual operation at opened contact.
  • Page 66: Motorheating On / Off, Function | 12D

    Operating Instructions Fcontrol – model series FXDM Programming • “D1 Inverting” “OFF” “Max. Speed” active at closed contact • “D1 Inverting” “ON” “Max. Speed” - - - - - active at opened contact Controller = 80 % = 0 .. 100 % D1 D1 15.05.2009...
  • Page 67: Freeze Function" = Maintain Momentary Modulation Value, Function

    Operating Instructions Fcontrol – model series FXDM Programming The active switch over of direction is indicated by the antenna symbol in the display. Actual value 1 Contact e.g. by digital input “Digital In 1” for factory setting “ clockwise rotation.”...
  • Page 68: Inverting Analog Inputs "E1" / "E2

    Operating Instructions Fcontrol – model series FXDM Programming Example for Mode “1.01” with speed setting signal 0 - 10 V Modus 1 Modus 1 [Hz] Example: “E1 min.” = 20 % The controller begins only at approx. 20% higher signal with minimal modulation.
  • Page 69: Function And Inverting For Relay Outputs "K1" And "K2

    Operating Instructions Fcontrol – model series FXDM Programming Example: mode speed controller, setting by external signal 100 % Min. 0 % Max. = 100 % Min. 35 % Max. = 85 % 50 % Min. 0 – 10 V 10 – 0 V 0 –...
  • Page 70: Programming Add-On Module Type Z-Modul-B

    Operating Instructions Fcontrol – model series FXDM Programming Group control (Group 2) Switching on fans depending on modulation 12K * Group control (Group 3) Switching on fans depending on modulation 13K * Group control (Group 4) Switching on fans depending on modulation For modes as controller higher 2.01...
  • Page 71: Networking Via Modbus

    Operating Instructions Fcontrol – model series FXDM Programming • 2 x relay outputs (“K3” and “K4”) Function programmable, e.g., for: Status signals, alarm indications, external malfunctions at the digital input, level-control threshold, input signal threshold, offset threshold (deviation between current and target value), group control.
  • Page 72: Limits

    Operating Instructions Fcontrol – model series FXDM Programming 9.11 Limits 9.11.1 Limit indication depending on modulation Following functions can be allocated to the limit indication no function Indication with the centralized fault of a programmed relay (IO allocation Controller function Function Warning symbol in display, “AL”...
  • Page 73: Limit Indication Depending On (Offset) To Setpoint

    Operating Instructions Fcontrol – model series FXDM Programming Both values for E1 (“E1 min” and “E1 max”) can be set independent of each other and act on a relay together if correspondingly programmed. If a function is activated or if a relay is allocated, both settings (“min”...
  • Page 74 Operating Instructions Fcontrol – model series FXDM Programming Offset 1, Offset 2 Both values for Offset 1 and Offset 2 can be set independent of each other and act on a relay together if correspondingly programmed. If a function is activated or if a relay is Offset 1 allocated both settings (Offset 1 and Offset 2) are initially at “OFF”.
  • Page 75: Motor Setup

    Operating Instructions Fcontrol – model series FXDM Programming 9.12 Motor Setup Menu group Motor Setup Motor Setup 9.12.1 Setting motor rated current MotorRatedCurr. Possible setting for the motor rated current. The setting for the “DC brake level” ( setting brake behaviour) refers to this setting.
  • Page 76 Operating Instructions Fcontrol – model series FXDM Programming = 50 Hz 100 % = 48.5 Hz edge = 10 % start [Hz] = 0 % start Analog In 1 0...10 V 0...20 mA 90 100 0...100 % PWM 26.07.2012 v_u_f_dia_fcontr_d.vsd...
  • Page 77: Setting For Rampup Time And Rampdown Time

    Operating Instructions Fcontrol – model series FXDM Programming 9.12.4 Setting for Rampup time and Rampdown time By separate menus for Rampup time and Rampdown time an adjustment is possible to individual system conditions. This function is switched behind the actual controller function.
  • Page 78: Setting Current Limit

    Operating Instructions Fcontrol – model series FXDM Programming 9.12.6 Setting Current limit As an additional safety function the device has a current limit, this can be adapted if necessary. The setting refers to the motor rated current of the device (100 % = setting: MotorRa- Current limit tedCurr.).
  • Page 79: Boost Function

    Operating Instructions Fcontrol – model series FXDM Programming Active brake mode is signaled by a bright triangle in the display. Frequency 9.12.8 Boost function The boost function5is an automatic voltage increase in case of dynamic demands on the control system. When using the square characteristic, the output voltage is increased to the value of the linear characteristic with the “Boost function”...
  • Page 80: Suppression Of Speeds

    Operating Instructions Fcontrol – model series FXDM Programming 9.12.10 Suppression of speeds Suppression of up to three speed ranges. Under certain circumstances, it is possible to prevent disturbing noises that can arise at certain speeds due to resonances. Example for suppression of 2 ranges (Idealized principle diagram)
  • Page 81: 10 Menu Tables

    Operating Instructions Fcontrol – model series FXDM Menu tables 10 Menu tables 10.1 Menues of operating modes Mode User Setting 2.01 4.01 1.01 3.01 3.03 5.01 2.03 2.02 2.05 4.02 6.01 1.02 3.02 3.04 5.02 2.04 4.03 Parameter Factory setting...
  • Page 82 Operating Instructions Fcontrol – model series FXDM Menu tables Mode User Setting 2.01 4.01 1.01 3.01 3.03 5.01 2.03 2.02 2.05 4.02 6.01 1.02 3.02 3.04 5.02 2.04 4.03 Parameter Factory setting - - - - - Setpoint 2 - - - - -...
  • Page 83 Operating Instructions Fcontrol – model series FXDM Menu tables Mode User Setting 2.01 4.01 1.01 3.01 3.03 5.01 2.03 2.02 2.05 4.02 6.01 1.02 3.02 3.04 5.02 2.04 4.03 Parameter Factory setting 1.02 = - - Step 5 value - - - 3.02 =...
  • Page 84 Operating Instructions Fcontrol – model series FXDM Menu tables Mode User Setting 2.01 4.01 1.01 3.01 3.03 5.01 2.03 2.02 2.05 4.02 6.01 1.02 3.02 3.04 5.02 2.04 4.03 Parameter Factory setting Group 4 ON value - - - - -...
  • Page 85 Operating Instructions Fcontrol – model series FXDM Menu tables Mode User Setting 2.01 4.01 1.01 3.01 3.03 5.01 2.03 2.02 2.05 4.02 6.01 1.02 3.02 3.04 5.02 2.04 4.03 Parameter Factory setting - - - - - E2 Mode - - - - -...
  • Page 86 Operating Instructions Fcontrol – model series FXDM Menu tables Mode User Setting 2.01 4.01 1.01 3.01 3.03 5.01 2.03 2.02 2.05 4.02 6.01 1.02 3.02 3.04 5.02 2.04 4.03 Parameter Factory setting Lmt E2 Hyst. - - - - -...
  • Page 87: Possible Allocation Of The Ios, Pins

    Operating Instructions Fcontrol – model series FXDM Menu tables Mode User Setting 2.01 4.01 1.01 3.01 3.03 5.01 2.03 2.02 2.05 4.02 6.01 1.02 3.02 3.04 5.02 2.04 4.03 Parameter Factory setting 0.00 V 0.00 V 0.00 V 0.00 V 0.00 V...
  • Page 88 Operating Instructions Fcontrol – model series FXDM Menu tables 10.2 Possible allocation of the IOs, PINs Analog outputs A / A2 Function Description function A / A2 Constant voltage +10 V proportional level control proportional input E1 proportional input E2 Group control only 2.03 Cooling function (not for Z-Modul-B)
  • Page 89 Operating Instructions Fcontrol – model series FXDM Menu tables Function Description Function E2 External Manual mode Digital outputs K1..K4 Function Description function K1, K2 ,K3*, K4* No function Relays remain always de-energized Operating indication (factory setting for “K1”, non inverting).
  • Page 90: 11 Diagnostics Menu

    Operating Instructions Fcontrol – model series FXDM Diagnostics menu PINs Function PIN 0010 Opening service menu, if PIN-protection activated Opening “setting”. PIN 1234 if “set protection” = “ON” ( Controller Setup) PIN 9090 Restore user setting Save user setting (corresponds function “Save user setup” = “ON”...
  • Page 91 Operating Instructions Fcontrol – model series FXDM Diagnostics menu E2-KTY Signal height at analog input E2 (Analog In 2) E2-Current E2-Voltage Signal height at analog input E3 (Analog In 3*) Status digital input 1 (Digital In 1) OFF = terminals D1 - D1 bridged ↔ ON = terminals D1 - D1 not bridged Status digital input 2 (Digital In 2) OFF = terminals D2 - D2 bridged ↔...
  • Page 92: Current Measurements

    Operating Instructions Fcontrol – model series FXDM Events / Fault signals 11.1 Current measurements Current measurements can be made without restrictions only on the motor side of the frequency inverter or EC controller. Line side measurements of the current may only be performed using true r.m.s. measuring equipment.
  • Page 93: Messages And Trouble Shooting

    Operating Instructions Fcontrol – model series FXDM Events / Fault signals 12.2 Messages and trouble shooting A momentary pending alarm or error message is indicated by a blinking indicator and appears alternately with the standard display. Operating conditions are indicated by the status LED with flashing code.
  • Page 94 Operating Instructions Fcontrol – model series FXDM Events / Fault signals Display Code* LED Code Relais switches Possible cause Reaction of Controller Opera- Adjustment internal Failure tion Controller loaded the User Setup automatically (if Warning message, operation available). E.g. in case of...
  • Page 95 Operating Instructions Fcontrol – model series FXDM Events / Fault signals Display Code* LED Code Relais switches Possible cause Reaction of Controller Opera- Adjustment internal Failure tion If the voltage supply returns within 5 s, the device automati- The device is provided cally switches itself back on.
  • Page 96: 13 Function Extension And Version Of Software

    Operating Instructions Fcontrol – model series FXDM Function extension and version of software Display Code* LED Code Relais switches Possible cause Reaction of Controller Opera- Adjustment internal Failure tion The device works with minimal or maximum modulation de- For Sensor 1 / Sensor 2...
  • Page 97: 14 Enclosure

    Operating Instructions Fcontrol – model series FXDM Enclosure 14 Enclosure 14.1 Technical data Rated cur- Rated cur- Rated tem- max. line Max. heat Noise ap- Weight Housing rent rent perature fuse dissipation prox. [kg] protec- approx. tion Output (I fundamen- tal compo- [°C]...
  • Page 98 Operating Instructions Fcontrol – model series FXDM Enclosure Rated cur- Rated cur- Rated tem- max. line Max. heat Noise ap- Weight Housing rent rent perature fuse dissipation prox. [kg] protec- approx. tion Output (I fundamen- tal compo- [°C] [dB] Type nent @ 50 (Part-No.)
  • Page 99: Versions Type-Lines Fcontrol

    • FXDM..A internal LCD-Multifunction display with plain language text. In IP20 for switch cabinet mounting • FXDM..E external terminal type AXG-1A(E), for start-up and setting necessary. • FXDM..AE internal LCD-Multifunction display with plain language text. 14.1.2 Max. load dependent on ambient temperature and line voltage.
  • Page 100: Connection Diagram

    Operating Instructions Fcontrol – model series FXDM Enclosure 14.2 Connection diagram Fcontrol FXDM...(A)M Kontaktbelastung Contact rating Adressierung max. AC 250 V 2 A °C Addressing TB/TP Digital Analog 24 V DC Analog Analog Digital Normal In 1 Out 1 In 1...
  • Page 101: Connection Suggestion For Several Motors With Motor Protection Unit Type Stdt

    Operating Instructions Fcontrol – model series FXDM Enclosure 14.2.1 Connection suggestion for several motors with motor protection unit type STDT • Total motor protection: Automatic cut-off by thermocontact actuation motor overtemperature. Button for Reset after malfunction. • Line protection: A thermal over current sensor and a magnetic short circuit releasing elements are the parts of the integral line protection.
  • Page 102: Dimensions [Mm]

    Operating Instructions Fcontrol – model series FXDM Enclosure 14.3 Dimensions [mm] FXDM2.5AM (IP54) FXDM5...18 (FXDM22) (IP54) L-BAL-E072-GB 1642 Index 008 Part.-No. 102/105...
  • Page 103 Operating Instructions Fcontrol – model series FXDM Enclosure FXDM32...50 (IP54 / IP65) FXDM32...50E (IP20) L-BAL-E072-GB 1642 Index 008 Part.-No. 103/105...
  • Page 104: Index

    Operating Instructions Fcontrol – model series FXDM 14.4 Index address mains Average calculation MAL1, MAL10 Maximum frequency MBG-30I, MBG-50I Minimum space requirement Base setup Minimum speed cut off bypass switching MODBUS Mode motor feed cable characteristic curve motor leads control cable...
  • Page 105: Manufacturer Reference

    Operating Instructions Fcontrol – model series FXDM Index 14.5 Manufacturer reference Our products are manufactured in accordance with the relevant international regulations. If you have any questions concerning the use of our products or plan special uses, please contact: ZIEHL-ABEGG SE Heinz-Ziehl-Straße...