ZIEHL-ABEGG Fcontrol FTET4AHMQ Operating Instructions Manual

ZIEHL-ABEGG Fcontrol FTET4AHMQ Operating Instructions Manual

Frequency inverter with integrated sine filter for 1 ~ fans in agriculture
Table of Contents

Advertisement

Quick Links

english
Fcontrol
FTET4/6/10AHMQ
Frequency inverter with integrated sine filter for 1 ~ fans in
agriculture
Operating Instructions
Keep for reference!
L-BAL-E094-GB 2022/47 Index 007
Part.-No.

Advertisement

Table of Contents
loading

Summary of Contents for ZIEHL-ABEGG Fcontrol FTET4AHMQ

  • Page 1 english Fcontrol FTET4/6/10AHMQ Frequency inverter with integrated sine filter for 1 ~ fans in agriculture Operating Instructions Keep for reference! L-BAL-E094-GB 2022/47 Index 007 Part.-No.
  • Page 2: Table Of Contents

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Content General notes ............. Meaning of the operating instructions .
  • Page 3 Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Multipurpose LC display and keyboard ........Menu operation .
  • Page 4: General Notes

    We do not accept any liability for possible errors or omissions in the information contained in data, illustrations or drawings provided. ZIEHL-ABEGG SE is not liable for damage due to misuse, incorrect use, improper use or as a consequence of unauthorized repairs or modifications.
  • Page 5: Explanations Of Symbols

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Safety instructions Explanations of symbols Safety instructions are highlighted with warning triangles and are depicted according to the degree of hazard as follows. Attention! General hazardous area. Death or severe injury or significant property damage can occur if the corresponding precautions are not taken! Danger due to electric current Danger by dangerous, electric voltage! Death or severe injury can occur if the corresponding...
  • Page 6: Work On The Device

    Use only genuine spare parts / genuine wearing parts / genuine accessories from ZIEHL-ABEGG.Th- ese parts were specifically designed for the device. There is no guarantee that parts from non-original sources are designed and manufactured in correspondence with load and safety requirements.
  • Page 7: Employment Of External Personnel

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Product overview Employment of external personnel Maintenance and service work are frequently carried out by external employees who often do not recognize the specific situations and the thus resulting dangers.These persons must be comprehen- sively informed about the hazards in their area of activity.
  • Page 8: Mounting

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Mounting 4 Mounting General notes Attention! The following points must be complied with during the mechanical installation to avoid causing a defect in the device due to assembly errors or environmental influences: • Before installation remove the device from the packing and check for any possible shipping damage! Start-up is not allowed in the case of transport damage! •...
  • Page 9: Installation Location For Agriculture

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Electrical installation Installation location for agriculture When using for animal keeping, do not install the device directly in the stable but in a separate room with a lower pollutant load. This helps to avoid damages caused by pollutant gases (e.g. ammonia fumes, hydrogen sulphide fumes).
  • Page 10: Mains Connection

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Electrical installation Mains connection 5.3.1 Mains voltage The mains connection is made at the terminals: PE, L1 and N. In this regard, it is essential to ensure that the mains voltage lies within the allowable tolerance specifications (see technical data and rating plate affixed to the side).
  • Page 11: Disconnection Between Controller And Motor (Repair Switch)

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Electrical installation 5.5.2 Disconnection between controller and motor (repair switch) Ideally, a repair switch should be installed before the controller (supply line disconnect). In case of complete shutdown (total load) after the controller this may take place under some circum- stances at full fan level of the controller.
  • Page 12: Control Output 0 - 10 V (A1, A2 A )

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Electrical installation For a high interference immunity a capacitor must be connected directly to the sensor (1nF parallel). With ZIEHL-ABEGG temperature sensors type TF.. (KTY81-210) a capacitor is integrated. Attention! Never apply line voltage to analog inputs!
  • Page 13: Relay Outputs (K1, K2)

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Controls and Menu 5.10 Relay outputs (K1, K2) The controller has two relay outputs (contact rating see technical data): • For Fault indication Relays K1 – Connection of the floating contacts to the terminals 11, 12, 14. –...
  • Page 14: Multipurpose Lc Display And Keyboard

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Controls and Menu Multipurpose LC display and keyboard 2 3 4 5 6 7 8 10.12.2013 v_display_erklaerung_ftet.vsd 1. Numeric display 5 digit Program key and open menu 2. Current derating active Menu selection, reduce value ▼...
  • Page 15: Menu Structure

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ The Installation menu Menu structure The main menus: Quick Info ventilation alarm heating , can be opened by briefly pressing the P-key. ▼ ▼ ▼ ▼ ▲ ▲ ▲ ▲ S:20.0° SH:94% Ventilation Alarm Heating Installation...
  • Page 16: Installation - Ventilation

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ The Installation menu Installation - Ventilation ↑ ▼+▲ ↓ Ventilation 7.2.1 Minimum speed cut off In some cases in which minimum air ventilation is not needed, this feature can be used to prevent an undercooling of the room. Msco Msco.
  • Page 17: Installation - Shutter

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ The Installation menu Installation - Shutter ↑ ▼+▲ ↓ Shutter Shutter input 0 = Sensor on E1 = Control via offset to setpoint ventilation (factory setting) 1 = Sensor on E2 = Control independent from the ventilation nominal value Shutter input Kl.
  • Page 18: Installation - Setpoint Derating

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ The Installation menu Installation – Setpoint derating ↑ ▼+▲ ↓ Setp. Derating Increase If the compartment temperature rises above the “setpoint” + the “control range”, the setpoint is increased via an automatic timer per hour by the adjustable value (e.g. 0.2 Increase K/h).
  • Page 19: Io Setup = Assignment Of Inputs And Outputs

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ The Installation menu IO Setup = Assignment of inputs and outputs ↑ ▼+▲ ↓ IO Setup Outdoor temperature OFF = No measurement of the supply air temperature. If ON = measurement of supply air temperature active. Sensor on “E2” is taken into Outdoor temperature consideration for the temperature alarm message (Adjustable alarm differential).
  • Page 20: Installation - Motorsetup

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ The Installation menu Output curve P1 Output curve P2 Output curve P3 Output curve P4 (18°) (36°) (54°) (72°) (90°) Output curve P5 04.08.2008 v_kennl_anlaog_ausg_6pkt.vsd Installation - Motorsetup 7.8.1 Menu “Motorsetup ” Menu group Motor Setup Motor Setup Attention! Settings for U/f characteristic may only be made when no motor modulation is present!
  • Page 21: Setting Motor Rated Current

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ The Installation menu Range2 max. - - - - Suppression3 Range3 max. - - - - Range3 max. - - - - 7.8.2 Setting motor rated current MotorRatedCurr. Possible setting for the motor rated current. The setting for the “DC brake level”...
  • Page 22: Setting For Rampup Time And Rampdown Time

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ The Installation menu Uout Ustart [Hz] Fedge 16.05.2007 Foff v_u_f_kennlinie.vsd Fmax Uout Output voltage Ustart Startvoltage Foff Shutdown Freq. Fedge Edgefrequency Fmax Maximum frequency L linear Q Square (factory setting) Startvoltage The start voltage is used to apply enough torque to the motors to insure they will run at low speed.
  • Page 23: Setting Current Limit

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ The Installation menu 0 .. 100 % 09.05.2007 v_hochlaufzeit_ruecklaufzeit.vsd 1 external Signal 2 Setting 3 Rampup time 4 Rampdown time 7.8.6 Setting Current limit As an additional safety function the device has a current limit, this can be adapted if necessary.
  • Page 24: Setting Boost Value

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ The Installation menu DC brake level Direct-current voltage level, generated for braking. The higher this value, the greater the braking effect. The setting is dependent on the size of the ventilator / motor. DC brake level Attention! Values that are too high, will result in an excessive braking effect and possibly lead to actuation of the overload shutoff.
  • Page 25: Installation - Diagnostic

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ The Installation menu Example for suppression of 2 ranges (Idealized principle diagram) 100 % 50 % 35 % max Setting depending on device type 15 % min in: %, Hz, rpm 09.05.2007 v_ausblendung_prz.vsd 100 % 50 % A Brake control...
  • Page 26: Commissioning

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Commissioning Version number internal motor controller (Menu dependent on device type available) 8 Commissioning Prerequisites for commissioning Attention! 1. You must mount and connect the device in accordance with the operating instructions. 2. Double check that all connections are correct. 3.
  • Page 27: Settings For Operation

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Settings for operation 9 Settings for operation Quickinfo, setpoint, min. and max. compartment temperatures ↑ ▼+▲ ↓ S:20.0° SH:94% Setpoint Setting range: 0...40 °C Factory setting: 20 °C Setpoint When a second sensor (optional) is connected to the input “E2” measured temper- ature.
  • Page 28: Setting Ventilation

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Settings for operation Setting Ventilation Ventilation ↑ The ventilation level control is additionally to the bargraph displayed here ▼+▲ in digits for informational purposes. ↓ Ventilation 9.2.1 For the regulation of the fan Setpoint Setting range: 0...40 °C Factory setting: 20 °C...
  • Page 29: For Throttle Shutter Control

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Settings for operation 9.2.2 For throttle shutter control The shutter function is used to control one throttle shutter in the chimney above or below the fan. Shutter offset Setpoint for throttle shutter (on 0 - 10 V output “Shutter”) = setpoint ± offset Setting range: -10.0...+10.0 K Shutter offset Factory setting: -1.0 K...
  • Page 30: Setpoint Derating

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Settings for operation 9.2.3 Setpoint derating Activation for automatic reduction (Setpoint automatic in summer) Setpoint derating OFF = Setpoint derating switched off Setp. Derating ON = Setpoint derating switched on Setp. Derating 05.08.2008 v_absenkauto_aktiv_pte.vsd 1 Display for automatic set point adaptation is active 2 New nominal set point with active automatic set point derating e.
  • Page 31: Temperature Monitoring Settings (Alarm Functions)

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Settings for operation Temperature monitoring settings (Alarm functions) Alarm Whether or not a malfunction is present is shown for informational purposes Alarm • OFF = currently no alarm pending • ON = Alarm is pending The pending alarm message is displayed alternating e.g.
  • Page 32: Settings For Heating

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Settings for operation Example for the alarm maximum message 1. Display actual-value alternates with an alarm message S:25°C SH:99% Overtemp. 2. In the menu group overview, “Alarm” “Alarm ON” appears alternately with the pending alarm message. Alarm Overtemp.
  • Page 33: Heating Control By Relay (Two-Point Mode)

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Settings for operation 9.4.1 Heating control by relay (two-point mode) 9.4.1.1 Example for two-position control independent of the ventilation nominal value (factory setting) • In installation menu “Mode 1” = Two-position controller, heating input = “0” =“E1” •...
  • Page 34: Example For Two-Position Control Independent Of The Ventilation Nominal Value

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Settings for operation 9.4.1.2 Example for two-position control independent of the ventilation nominal value • In installation menu “Mode 1” = Two-position controller, heating input: “1” =“E2” • Current heating value from sensor on input “E2” Heating Setpoint Heater switch-on adjustable as a separate setpoint (i.e., in °C) Setting range: -10.0...+40.0 °C...
  • Page 35 Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Settings for operation Heating Pband Setting range: 0.1..10.0 K Factory setting: 2.0 K Heating Pband Heating minimum Setting range: 0...100 % Factory setting: 0 % Heating minimum Heating maximum Setting range: 0...100 % Factory setting: 100 % Heating maximum Heating or cooling function dependent on the setting in the installation menu “Heat actual <...
  • Page 36: Menu Table

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Menu table 10 Menu table Information The individually made programming can be saved with PIN 9091 and restored with PIN 9090 (Quickinfo Menu- PIN). Attention! Entering PIN 9095 completely resets the device back into its delivered condition. Any changes that have been made to the settings are thus lost! ▼...
  • Page 37 Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Menu table Parameter Factory setting Compartment setting Installation Ventilation Msco MSCO value -5.0 K Shutter Shutter input Kl. Val<Set=+ Ventilation link Heating Heating mode Heating input Heat.Val<Set=+ Setp. Derating Increase 0.2 K/h Derating 0.1 K/h Max.
  • Page 38 Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Menu table Parameter Factory setting Compartment setting Current limit 120 % DC brake mode DC brake time 5 sek DC brake level 10 % Boost Value 15.0 % Suppression1 Range1 min. - - - - Range1 max.
  • Page 39: Malfunctions / Trouble Shooting

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Malfunctions / trouble shooting 11 Malfunctions / trouble shooting A momentary pending alarm or error message appears alternately with the standard display. Display Cause Reaction of Controller Remedial measures All displays remain con- Defect in device Not possible to remedy.
  • Page 40 Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Malfunctions / trouble shooting Display Cause Reaction of Controller Remedial measures Temperature management active At sinking temperature the controller re- starts. The device has an active temperature management to protect it from damage Check the temperature in the device via due to too high inside temperatures.
  • Page 41: Enclosure

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Enclosure 12 Enclosure 12.1 Technical data Type FTET4AHMQ FTET6AHMQ FTET10AHMQ Part-No. 308131 308132 308133 Rated current output* {1} Rated current input {2} 10,8 Max. load limit integral of cut-in current {2} s] 0,6 Max.
  • Page 42: Performance Reduction During Elevated Ambient Temperatures

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Enclosure 12.1.1 Performance reduction during elevated ambient temperatures The maximum permissible temperature for the rated current at rated voltage is specified as rated temperature. Since the dissipation of the power loss (heat development) in the device is decisively dependent on the ambient temperature, the max.
  • Page 43: Connection Diagram

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Enclosure 12.2 Connection diagram Fcontrol FTET4/6/10AHMQ Kontaktbelastung Contact rating max. AC 250 V 2 A Störung / Alarm Heizung Fault / Indication Heating Ausgang TF.. TF.. Output 0...10 V = 6 mA) Ausgang KTY 81-210 Output PT 1000...
  • Page 44: Dimensions [Mm]

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ Enclosure 12.3 Dimensions [mm] FTET4AHMQ FTET6/10AHMQ L-BAL-E094-GB 2022/47 Index 007 Part.-No. 44/46...
  • Page 45: Index

    Operating Instructions Fcontrol – model series FTET4/6/10AHMQ 12.4 Index alarm list PIN codes alarm message power electronics Assignment proportional controller protected PT1000 characteristic curve chimney control cable Rampdown time curve Rampup time Relay outputs residual current protective DC-brake device diagnostics menu resonances direction of rotation servo motor...
  • Page 46: Manufacturer Reference

    Manufacturer reference Our products are manufactured in accordance with the relevant international regulations. If you have any questions concerning the use of our products or plan special uses, please contact: ZIEHL-ABEGG SE Heinz-Ziehl-Straße 74653 Künzelsau phone: +49 (0) 7940 16-0 info@ziehl-abegg.de...