Section 1
General Information

Keypad Mode

3-12 Installation
In the Keypad Operating mode:
To operate in the Keypad mode, set the Level 1 Input block, OPERATING MODE
parameter to KEYPAD. In this mode, only two Opto inputs can be active. Both analog
outputs (at J1A) remain active.
If the Level 2 PROTECTION block, EXTERNAL TRIP and LOCAL ENABLE INPUT
parameters remain OFF (factory setting), no terminal strip wiring is required.
1.
The External Trip Opto Input at J1B-16 is active if the Level 2 PROTECTION
block, EXTERNAL TRIP parameter is set to ON. If the Level 2 PROTECTION
block, EXTERNAL TRIP parameter is programmed "ON", make connections as
shown in Figure 3-7.
2.
The Local Enable Opto Input at J1B-8 is active if the Level 2 PROTECTION
block, LOCAL INP ENABLE parameter is set to ON. If the Level 2
PROTECTION block, LOCAL INP ENABLE parameter is programmed "ON",
make connections as shown in Figure 3-7.
The STOP key can operate in two ways:
Press STOP key one time to brake or coast to stop.
Press STOP key two times to disable control.
MN1230