Integrate the meter with the control system
2.4.4 Fault indication with the discrete output
To indicate faults via the discrete output, set parameters as follows:
▪
Discrete Output Source = Fault
▪
Discrete Output Fault Action = None
Note
If Discrete Output Source is set to Fault and a fault occurs, the discrete output is always ON. The
setting of Discrete Output Fault Action is ignored.
2.5
Configure digital communications
Display
OFF-LINE MAINT→OFF-LINE CONFG→COMM
ProLink II
ProLink→Configuration→Device
Communicator
5,3,4
Detailed Setup→Config Outputs→HART Output
The digital communications parameters control how the transmitter will communicate using digital
communications.
The Model 2700 transmitter with intrinsically safe outputs supports the following types of digital
communications:
▪
HART/Bell 202 over the primary mA terminals
▪
Modbus/RS-485 via the service port
Digital Communications Fault Action applies to all types of digital communications.
Note
The service port responds automatically to a wide range of connection requests. It is not
configurable.
2.5.1 Configure HART/Bell 202 communications
Display
OFF-LINE MAINT→OFF-LINE CONFG→COMM
ProLink II
ProLink→Configuration→Device→Digital Comm Settings
Communicator
5,3,4
Detailed Setup→Config Outputs→HART Output
HART/Bell 202 communications parameters support HART communication with the transmitter's
primary mA terminals over a HART/Bell 202 network.
20
Micro Motion Model 2700 Transmitters with Intrinsically Safe Outputs