E.2 DNP POINT LISTS
E.2DNP POINT LISTS
The DNP binary input data points are configured through the
LISTS
BINARY INPUT / MSP POINTS
freeze function is performed on a binary counter point, the frozen value is available in the corresponding frozen counter
point.

BINARY INPUT POINTS

Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read), 22 (assign class)
Static Variation reported when variation 0 requested: 2 (Binary Input with status), Configurable
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable
Change Event Scan Rate: 8 times per power system cycle
Change Event Buffer Size: 500
Default Class for All Points: 1
E
E-8
PRODUCT SETUP
menu. Refer to the Communications section of Chapter 5 for additional details. When a
T35 Transformer Protection System
APPENDIX E
E.2.1 BINARY INPUT POINTS


COMMUNICATIONS
DNP / IEC104 POINT
GE Multilin