GE T35 UR Series Instruction Manual page 440

Transformer protection system
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 26 of 52)
ADDR
REGISTER NAME
5D07
Ground Time Overcurrent 1 Block
5D09
Ground Time Overcurrent 1 Target
5D0A
Ground Time Overcurrent 1 Events
5D0B
Reserved (6 items)
5D11
...Repeated for Ground Time Overcurrent 2
B
5D22
...Repeated for Ground Time Overcurrent 3
5D33
...Repeated for Ground Time Overcurrent 4
5D44
...Repeated for Ground Time Overcurrent 5
5D55
...Repeated for Ground Time Overcurrent 6
CT Fail (Read/Write Setting) (6 modules)
5E6C
CT Fail 1 Function
5E6D
CT Fail 1 Block
5E6F
CT Fail 1 Current Source 1
5E70
CT Fail 1 Current Pickup 1
5E71
CT Fail 1 Current Source 2
5E72
CT Fail 1 Current Pickup 2
5E73
CT Fail 1 Voltage Source
5E74
CT Fail 1 Voltage Pickup
5E75
CT Fail 1 Pickup Delay
5E76
CT Fail 1 Target
5E77
CT Fail 1 Events
5E78
...Repeated for CT Fail 2
5E84
...Repeated for CT Fail 3
5E90
...Repeated for CT Fail 4
5E9C
...Repeated for CT Fail 5
5EA8
...Repeated for CT Fail 6
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group 1)
5F71
Setting Groups Block
5F73
FlexLogic Operands to Activate Groups 2 through 6 (5
items)
5F7D
Setting Group Function
5F7E
Setting Group Events
Setting Groups (Read Only)
5F7F
Current Setting Group
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
5F94
Setting Group 2 Name
5F9C
Setting Group 3 Name
5FA4
Setting Group 4 Name
5FAC
Setting Group 5 Name
5FB4
Setting Group 6 Name
Transformer Percent Differential (Read/Write Grouped Setting)
61C0
Percent Differential Function
61C1
Percent Differential Pickup
61C2
Percent Differential Slope 1
61C3
Percent Differential Break 1
61C4
Percent Differential Break 2
61C5
Percent Differential Slope 2
61C6
Inrush Inhibit Function
61C7
Inrush Inhibit Level
61C8
Overexcitation Inhibit Function
61C9
Overexcitation Inhibit Level
61CA
Percent Differential Block
B-34
RANGE
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 4294967295
0 to 5
0 to 2
0 to 5
0 to 2
0 to 5
0 to 2
0 to 65.535
0 to 2
0 to 1
0 to 5
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 5
---
---
---
---
---
---
0 to 1
0.05 to 1
15 to 100
1 to 2
2 to 30
50 to 100
0 to 2
1 to 40
0 to 1
1 to 40
0 to 4294967295
T35 Transformer Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F300
---
1
F167
pu
0.1
F001
---
1
F167
pu
0.1
F001
---
1
F167
pu
0.01
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F001
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F001
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
1
F102
pu
0.001
F001
%
1
F001
pu
0.001
F001
pu
0.001
F001
%
1
F001
---
1
F168
1 (Adapt. 2nd)
%fo
0.1
F001
---
1
F169
%fo
0.1
F001
---
1
F300
DEFAULT
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0
0 (SRC 1)
2
1 (SRC 2)
2
0 (SRC 1)
20
1000
0 (Self-reset)
0 (Disabled)
0
0
0
0 (Disabled)
0 (Disabled)
0
(none)
(none)
(none)
(none)
(none)
(none)
0 (Disabled)
100
25
2000
8000
100
200
0 (Disabled)
100
0
GE Multilin