User-Programmable Self Tests - GE T35 UR Series Instruction Manual

Transformer protection system
Table of Contents

Advertisement

5 SETTINGS
Refer to the LED indicators section in chapter 4 for additional information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the
Reset" (the default setting), the LED illumination will track the state of the selected LED operand. If the
"Latched", the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a communica-
tions channel, or from any programmed operand, even if the LED operand state de-asserts.
Table 5–4: RECOMMENDED SETTINGS FOR USER-PROGRAMMABLE LEDS
SETTING
PARAMETER
LED 1 operand
SETTING GROUP ACT 1
LED 2 operand
SETTING GROUP ACT 2
LED 3 operand
SETTING GROUP ACT 3
LED 4 operand
SETTING GROUP ACT 4
LED 5 operand
SETTING GROUP ACT 5
LED 6 operand
SETTING GROUP ACT 6
LED 7 operand
Off
LED 8 operand
Off
LED 9 operand
Off
LED 10 operand
Off
LED 11 operand
Off
LED 12 operand
Off
See the figure in the Control Groups section of the Control Elements section later in this chapter for an example of group
activation.
For user-programmable self-tests for CyberSentry, use the Setup > Security > Supervisory menu instead.
PATH: SETTINGS
PRODUCT SETUP
 USER-PROGRAMMABLE
 SELF TESTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
SETTING
LED 13 operand
LED 14 operand
LED 15 operand
LED 16 operand
LED 17 operand
LED 18 operand
LED 19 operand
LED 20 operand
LED 21 operand
LED 22 operand
LED 23 operand
LED 24 operand


USER-PROGRAMMABLE SELF TESTS

DIRECT RING BREAK
FUNCTION: Enabled
DIRECT DEVICE OFF
FUNCTION: Enabled
REMOTE DEVICE OFF
FUNCTION: Enabled
FIRST ETHERNET FAIL
FUNCTION: Disabled
SEC. ETHERNET FAIL
FUNCTION: Disabled
THIRD ETHERNET FAIL
FUNCTION: Disabled
BATTERY FAIL
FUNCTION: Enabled
SNTP FAIL
FUNCTION: Enabled
IRIG-B FAIL
FUNCTION: Enabled
PTP FAIL
FUNCTION: Enabled
T35 Transformer Protection System
5.2 PRODUCT SETUP
LED 1 TYPE
LED 1 TYPE
PARAMETER
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
5.2.12 USER-PROGRAMMABLE SELF TESTS
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
setting is "Self-