5 SETTINGS
PATH: SETTINGS
PRODUCT SETUP
ANALOG INPUT / MME
POINTS
MESSAGE
MESSAGE
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first "Off" value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first "Off" point are ignored.
NOTE
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the T35 is restarted.
NOTE
i) IEC 61850 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
IEC 61850 PROTOCOL
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The T35 Transformer Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details.
GE Multilin
COMMUNICATIONS
DNP / IEC104 POINT LISTS
Point:
0
Off
Point:
1
Off
↓
Point:
255
Off
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE / GOOSE
CONFIGURATION
SERVER
CONFIGURATION
IEC 61850 LOGICAL
NODE NAME PREFIXES
MMXU DEADBANDS
GGIO1 STATUS
CONFIGURATION
GGIO2 CONTROL
CONFIGURATION
GGIO4 ANALOG
CONFIGURATION
GGIO5 UINTEGER
CONFIGURATION
REPORT CONTROL
CONFIGURATION
XCBR
CONFIGURATION
XSWI
CONFIGURATION
T35 Transformer Protection System
5.2 PRODUCT SETUP
ANALOG INPUT / MME POINTS
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
5
5-31