Dnp Point Lists; Binary Input Points - GE M60 UR Series Instruction Manual

Motor protection system
Table of Contents

Advertisement

F.2 DNP POINT LISTS
F.2DNP POINT LISTS
The DNP binary input data points are configured through the
LISTS
BINARY INPUT / MSP POINTS
tion is performed on a binary counter point, the frozen value is available in the corresponding frozen counter point.

BINARY INPUT POINTS

Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read), 22 (assign class)
Static Variation reported when variation 0 requested: 2 (Binary Input with status), Configurable
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable
Change Event Scan Rate: 8 times per power system cycle
Change Event Buffer Size: 500
Default Class for All Points: 1
F
F-8
PRODUCT SETUP
menu. See the Communications section of Chapter 5 for details. When a freeze func-
M60 Motor Protection System
APPENDIX F
F.2.1 BINARY INPUT POINTS


COMMUNICATIONS
DNP / IEC104 POINT
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents