5.2 PRODUCT SETUP
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first "Off" value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first "Off" point are ignored.
NOTE
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the M60 is restarted.
NOTE
k) IEC 61850 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 IEC 61850 PROTOCOL
5
The M60 Motor Protection System is provided with optional IEC 61850 communications capability. This
feature is specified as a software option at the time of ordering. See the Order Codes section in chapter 2
for details.
Use independent ports for IEC 61850 communication and take care when configuring the settings,
else loss of protection or misoperation of the relay can result.
The M60 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported
over two protocol stacks: TCP/IP over Ethernet. The M60 operates as an IEC 61850 server. The Remote Inputs and Out-
puts section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS
PRODUCT SETUP
 GSSE / GOOSE
 CONFIGURATION
5-40

COMMUNICATIONS
 GSSE / GOOSE
 CONFIGURATION
 SERVER
MESSAGE
 CONFIGURATION
 IEC 61850 LOGICAL
MESSAGE
 NODE NAME PREFIXES
 MMXU DEADBANDS
MESSAGE
 GGIO1 STATUS
MESSAGE
 CONFIGURATION
 GGIO2 CONTROL
MESSAGE
 CONFIGURATION
 GGIO4 ANALOG
MESSAGE
 CONFIGURATION
 GGIO5 UINTEGER
MESSAGE
 CONFIGURATION
 REPORT CONTROL
MESSAGE
 CONFIGURATION
 XCBR
MESSAGE
 CONFIGURATION
 XSWI
MESSAGE
 CONFIGURATION

COMMUNICATIONS
 TRANSMISSION
 RECEPTION
MESSAGE
M60 Motor Protection System

IEC 61850 PROTOCOL

IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
5 SETTINGS
GE Multilin