GE M60 UR Series Instruction Manual page 505

Motor protection system
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 24 of 66)
ADDR
REGISTER NAME
4494
...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (6 Modules)
4500
Phase VT 1 Connection
4501
Phase VT 1 Secondary
4502
Phase VT 1 Ratio
4504
Auxiliary VT 1 Connection
4505
Auxiliary VT 1 Secondary
4506
Auxiliary VT 1 Ratio
4508
...Repeated for VT Bank 2
4510
...Repeated for VT Bank 3
4518
...Repeated for VT Bank 4
4520
...Repeated for VT Bank 5
4528
...Repeated for VT Bank 6
Source Settings (Read/Write Setting) (6 Modules)
4580
Source 1 Name
4583
Source 1 Phase CT
4584
Source 1 Ground CT
4585
Source 1 Phase VT
4586
Source 1 Auxiliary VT
4587
...Repeated for Source 2
458E
...Repeated for Source 3
4595
...Repeated for Source 4
459C
...Repeated for Source 5
45A3
...Repeated for Source 6
Power System (Read/Write Setting)
4600
Nominal Frequency
4601
Phase Rotation
4602
Frequency And Phase Reference
4603
Frequency Tracking Function
Breaker Control (Read/Write Settings) (4 Modules)
47D0
Breaker 1 Function
47D1
Breaker 1 Name
47D4
Breaker 1 Mode
47D5
Breaker 1 Open
47D7
Breaker 1 Close
47D9
Breaker 1 Phase A / Three-pole Closed
47DB
Breaker 1 Phase B Closed
47DD
Breaker 1 Phase C Closed
47DF
Breaker 1 External Alarm
47E1
Breaker 1 Alarm Delay
47E3
Breaker 1 Pushbutton Control
47E4
Breaker 1 Manual Close Recall Time
47E6
Breaker 1 Out of Service
47E8
Breaker 1 Block Open
47EA
Breaker 1 Block Close
47EC
Breaker 1 Phase A / Three-pole Opened
47EE
Breaker 1 Phase B Opened
47F0
Breaker 1 Phase C Opened
47F2
Breaker 1 Operate Time
47F3
Breaker 1 Events
47F4
Reserved
47F5
...Repeated for breaker 2
481A
...Repeated for breaker 3
483F
...Repeated for breaker 4
GE Multilin
RANGE
0 to 1
25 to 240
1 to 24000
0 to 6
25 to 240
1 to 24000
0 to 1
0 to 63
0 to 63
0 to 63
0 to 63
25 to 60
0 to 1
0 to 5
0 to 1
0 to 1
---
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 1
0 to 65535
M60 Motor Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F100
V
0.1
F001
:1
1
F060
---
1
F166
V
0.1
F001
:1
1
F060
---
---
F206
---
1
F400
---
1
F400
---
1
F400
---
1
F400
Hz
1
F001
---
1
F106
---
1
F167
---
1
F102
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F003
---
1
F102
s
0.001
F003
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
---
1
F102
s
1
F001
DEFAULT
0 (Wye)
664
1
B
1 (Vag)
664
1
"SRC 1"
0
0
0
0
60
0 (ABC)
0 (SRC 1)
1 (Enabled)
0 (Disabled)
"Bkr 1"
0 (3-Pole)
0
0
0
0
0
0
0
0 (Disabled)
0
0
0
0
0
0
0
70
0 (Disabled)
0
B-31