GE M60 UR Series Instruction Manual page 183

Motor protection system
Table of Contents

Advertisement

5 SETTINGS
l) WEB SERVER HTTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 WEB SERVER
 HTTP PROTOCOL
The M60 contains an embedded web server and is capable of transferring web pages to a web browser such as Internet
Explorer or Firefox. The web pages are organized as a series of menus that can be accessed starting at the M60 "Main
Menu". Web pages are available showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault
reports, and so on. First connect the UR and a computer to an Ethernet network, then enter the IP address of the M60 into
the "Address" box of the web browser.
When the port is set to 0, the change takes effect when the M60 is restarted.
NOTE
m) TFTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 TFTP PROTOCOL
MESSAGE
MESSAGE
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the M60 over a network. The M60 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file
obtained from the M60 contains a list and description of all available files (event records, oscillography, etc.).
When the
TFTP MAIN UDP PORT NUMBER
NOTE
GE Multilin


COMMUNICATIONS
WEB SERVER HTTP PROTOCOL
HTTP TCP PORT
NUMBER:
80


COMMUNICATIONS
TFTP PROTOCOL
TFTP MAIN UDP PORT
NUMBER:
69
TFTP DATA UDP PORT 1
NUMBER:
0
TFTP DATA UDP PORT 2
NUMBER:
0
is set to 0, the change takes effect when the M60 is restarted.
M60 Motor Protection System
5.2 PRODUCT SETUP
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1