5 SETTINGS
Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive – as such, they cannot be used
simultaneously. Once teleprotection inputs and outputs are enabled, direct inputs and outputs are blocked, and vice
versa.
NOTE
NUMBER OF TERMINALS: Specifies whether the teleprotection system operates between two peers or three peers.
NUMBER OF CHANNELS: Specifies how many channels are used. If the
system), set the
NUMBER OF CHANNELS
"2" (redundant channels).
LOCAL RELAY ID NUMBER, TERMINAL 1 RELAY ID NUMBER, and TERMINAL 2 RELAY ID NUMBER: In installa-
tions that use multiplexers or modems, it is desirable to ensure that the data used by the relays protecting a given line
is from the correct relays. The teleprotection function performs this check by reading the message ID sent by transmit-
ting relays and comparing it to the programmed ID in the receiving relay. This check is also used to block inputs if inad-
vertently set to loopback mode or data is being received from a wrong relay by checking the ID on a received channel.
If an incorrect ID is found on a channel during normal operation, the
FlexLogic operand is set, driving the event with the same name and blocking the teleprotection inputs. For commis-
sioning purposes, the result of channel identification is also shown in the
CHANNEL CONFIGURATION
is not to be checked. On two- terminals two-channel systems, the same
both channels; as such, only the
PATH: SETTINGS
PRODUCT SETUP
 INSTALLATION
MESSAGE
To safeguard against the installation of a relay without any entered settings, the unit will not allow signaling of any output
relay until
is set to "Programmed". This setting is defaulted to "Not Programmed" when at the factory. The
RELAY SETTINGS
self-test error message is displayed until the relay is put into the "Programmed" state.
UNIT NOT PROGRAMMED
The
setting allows the user to uniquely identify a relay. This name will appear on generated reports.
RELAY NAME
GE Multilin
to "2". For a two-terminal system, the
actual value. The default value of "0" for the
TERMINAL 1 ID NUMBER


INSTALLATION

RELAY SETTINGS:
Not Programmed
RELAY NAME:
Relay-1
M60 Motor Protection System
NUMBER OF TERMINALS
NUMBER OF CHANNELS
TELEPROT CH1 ID FAIL

STATUS
LOCAL RELAY ID NUMBER
LOCAL RELAY ID NUMBER
has to be programmed on the receiving end.
Range: Not Programmed, Programmed
Range: up to 20 alphanumeric characters
5.2 PRODUCT SETUP
is "3" (three-terminal
can set to "1" or
or
TELEPROT CH2 ID FAIL

CHANNEL TESTS
VALIDITY OF
indicates that relay ID
is transmitted over
5.2.18 INSTALLATION
5-95