5.7 CONTROL ELEMENTS
d) RESTART DELAY
PATH: SETTINGS
CONTROL ELEMENTS
RESTART DELAY
The
RESTART DELAY MIN TIME
element asserts the
RESTART DELAY OP
ment uses motor status asserted by the thermal model element. The thermal protection must be configured properly in
order for this function to operate.
5
PATH: SETTINGS
CONTROL ELEMENTS
REDUCED VOLTAGE
STARTING
5-230
START SUPERVISION
RESTART DELAY
FUNCTION: Disabled
RESTART DELAY
MESSAGE
MIN TIME: 0 s
RESTART DELAY BLOCK:
MESSAGE
Off
RESTART DELAY
MESSAGE
TARGET: Self-reset
RESTART DELAY
MESSAGE
EVENTS: Disabled
setting specifies the lockout time to start the motor after motor was stopped. The restart delay
FlexLogic operand for
Figure 5–116: RESTART DELAY SCHEME LOGIC
REDUCED VOLTAGE STARTING
REDUCED VOLTAGE
STARTING: Disabled
TRANSITION MODE:
MESSAGE
Current Only
REDUCED VOLT FLA:
MESSAGE
125% FLA
REDUCED VOLT TIMER:
MESSAGE
10.0 s
REDUCED VOLT BLOCK:
MESSAGE
Off
REDUCED VOLT TARGET:
MESSAGE
Self-reset
REDUCED VOLT EVENTS:
MESSAGE
Disabled
M60 Motor Protection System
RESTART DELAY
Range: Disabled, Enabled
Range: 0 to 50000 s in steps of 1
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
after the motor stopped. The ele-
RESTART DELAY MIN TIME
5.7.8 REDUCED VOLTAGE STARTING
Range: Disabled, Enabled
Range: Current Only, Current or Timer,
Current and Timer
Range: 25 to 300% FLA in steps of 1
Range: 1.0 to 600.0 s in steps of 0.1
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS
GE Multilin