GE M60 UR Series Instruction Manual page 296

Motor protection system
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
SETTING
MOTOR LINE SOURCE
VOLTAGE CONNECTION
Wye
Vag
Vbg
Vcg
SETTING
SPEED2 MOTOR SOURCE
VOLTAGE CONNECTION
Wye
Vag
Vbg
Vcg
SETTING
SPEED2 MOTOR SWITCH
SETTING
2-SPEED MOTOR
PROTECTION
i) TWO-SPEED MOTOR ACCELERATION TIME
5

PATH: SETTINGS
GROUPED ELEMENTS
SPEED2 ACCELERATION TIME
 SPEED2
 ACCELERATION TIME
If the speed 2 acceleration time functionality is enabled, the element will read current from the source selected for speed 2
by the

SETTINGS
speed 1 to speed 2.
Acceleration time settings and functionality at speed 2 are identical to those of speed 1 and are described in the
Acceleration time sub-section. This applies to the
and
NOTE
SPEED2 ACCEL MODE
Two additional setting define the transition between speeds. A two-speed motor is usually started at a low speed (speed 1)
and then switched to a higher speed (speed 2) when required. When the motor starts directly at high speed, then the
SPEED2 ACCELERATION TIME
low-to-high speed setting, the
switched from high speed to low speed, the
setting to allow inputs for control logic of contactors and breakers at both speeds. FlexLogic operands
SWITCH 2-1 DELAY
required for contactor and breaker control are provided. The acceleration time at speed 2 becomes functional only if the
acceleration time at speed 1 is enabled. When the acceleration time at any speed is not required, it can be permanently
blocked.
5-168
= Ia
= Ib
= Ic
Delta
Vab
Vbc
Vca
= Ia
= Ib
= Ic
Delta
Vab
Vbc
Vca
Off = 0
AND
Enabled = 1
Figure 5–74: TWO-SPEED MOTOR THERMAL MODEL LOGIC
SETTING GROUP 1(6)
SPEED2 ACCELERATION
CURRENT: 6.00 x FLC
SPEED2 ACCELERATION
MESSAGE
TIME: 10.00 s
SPEED2 ACCEL MODE:
MESSAGE
Definite Time
SPEED2 ACCEL TIME FR
MESSAGE
SPEED 1-2: 10.00 s
SPEED2 ACCEL BLOCK:
MESSAGE
Off


SYSTEM SETUP
MOTOR
settings.
setting specifies the maximum acceleration time at speed 2. When motor is switched from a
SPEED2 TIMER FROM SPEED 1-2
SPEED2 TRANS 2-1 OP
M60 Motor Protection System
Ia
Ib
Ic
Thermal model,
voltage dependent
Va
Vb
Vc
Thermal model
Thermal model
settings, speed 1
settings, speed 2
Off
On
ACTIVE
SETTING
SPEED2 SWITCH 2-1
DELAY
0
T
RST

MOTOR
TWO-SPEED MOTOR
Range: 1.00 to 10.00
Range: 0.05 to 180.00 s in steps of 0.01
Range: Definite Time, Adaptive
Range: 0.05 to 180.00 s in steps of 0.01
Range: FlexLogic operand
setting when the motor is switched from
2-SPEED MOTOR SOURCE
SPEED2 ACCELERATION CURRENT
setting specifies the acceleration time. When motor is
FlexLogic operand is set for time defined by the
5 SETTINGS
FLEXLOGIC OPERAND
MOTOR SPD2 TR 2-1 OP
833020A1.CDR
FLC in steps of 0.01
,
SPEED2 ACCELERATION TIME
SPEED2
GE Multilin