IEC 61850/MMS
(RSR20/RSR30/MACH1000)
4.2.3

Monitoring the device

The IEC61850/MMS server integrated into the device allows you to monitor
multiple statuses of the device by means of the Report Control Block (RCB).
Up to 5 MMS clients can register for a Report Control Block at the same time.
The device allows the following statuses to be monitored:
Class
RCB object
LN LPHD
PwrSupAlm
TmpAlm
PhyHealth
LN LBRI
Health
RstpRoot
RstpTopoCnt
LN LCCH
ChLiv
LN LPCP
PhyHealth
Table 18: Statuses of the device that can be monitored with IEC 61850/MMS
66
4.2 Integration into a Control System
Description
Changes when one of the redundant power supplies fails or
starts operating again.
Changes when the temperature measured in the device
exceeds or falls below the set temperature thresholds.
Changes when the status of the "LPHD.PwrSupAlm" or
"LPHD.TmpAlm" RCB object changes.
Changes when the status of the "LPHD.PwrSupAlm" or
"LPHD.TmpAlm" RCB object changes.
Changes when the device takes over or relinquishes the role
of the root bridge.
Changes when the topology changes due to a change of the
root bridge.
Changes when the link status of the physical port changes.
Changes when the link status of the physical port changes.
UM IndustProtocol
Release 9.0 02/2015