Instruction book
3
Elektronikon® controller
3.1
Elektronikon
Control panel
Introduction
In general, the Elektronikon
• Controlling the compressor
• Protecting the compressor
• Monitoring components subject to service
• Automatic restart after voltage failure (made inactive)
Automatic control of the compressor
The regulator maintains the net pressure between programmable limits by automatically loading and
unloading the compressor. A number of programmable settings, e.g. the unloading and loading pressures,
the minimum stop time and the maximum number of motor starts are taken into account.
The regulator stops the compressor whenever possible to reduce the power consumption and restarts it
automatically when the net pressure decreases. If the expected unloading period is to short, the compressor
is kept running to prevent too short stand-still periods.
Protecting the compressor
Shutdown
If the compressor element outlet temperature exceeds the programmed shutdown level, the compressor will
be stopped. This will be indicated on the display of the regulator. The compressor will also be stopped in
case of overload of the drive motor.
Air-cooled compressors will also be stopped in the event of overload of the fan motor.
Shutdown warning
A shutdown warning level is a programmable level below the shutdown level.
API459842
®
regulator
®
regulator has following functions:
Before remedying, consult the
Safety precautions.
25