T91 User's Manual
14: Charger boost voltage setting
Interface
15: Charger float voltage setting
Interface
16: EPO logic setting
Interface
17: External output isolation transformer connection
Interface
18: Display setting for autonomy time
Interface
Xtreme Power Conversion Corporation
Settings
Parameter 2: Set up the charger boost voltage.
2.25-2.40: setting the charger boost voltage from 2.25
V/cell to 2.40V/cell. (Default: 2.36V/cell)
Settings
Parameter 2: Set up the charger float voltage.
2.20-2.33: setting the charger float voltage from 2.20
V/cell to 2.33V/cell. (Default: 2.28V/cell)
Settings
Parameter 2: Set up the EPO function control logic.
AO: Active Open (Default). When AO is selected as EPO logic, it will acti-
vate EPO function with Pin 1 and Pin 2 in open status.
AC: Active Close. When AC is selected as EPO logic, it will activate EPO
function with Pin 1 and Pin 2 in close status.
Settings
Parameter 2: Allow or disallow external output isolation transformer
connection.
ENA: If selected, it's allowed to connect to an external output isolation
transformer.
DIS: If selected, it's not allowed to connect to external output isolation
transformer. (Default)
Settings
Parameter 2: Set up the display setting for autonomy time
EAT: If EAT is selected, it will display the remaining autonomy time. (De-
fault)
RAT: If RAT is selected, it will show accumulated autonomy time so far.
Uninterruptible Power Supply
Page 23