Xtreme Power Conversion 1000VA User & Installation Manual page 21

T91 unity
Hide thumbs Also See for 1000VA:
Table of Contents

Advertisement

T91 User's Manual
08: Bypass frequency range setting
Interface
09: Programmable outlets enable/disable
Interface
10: Programmable outlets setting
Interface
Xtreme Power Conversion Corporation
Settings
Parameter 2: Set the acceptable high frequency point and acceptable
low frequency point for Bypass mode by pressing
the Down key or Up key.
HLS: Bypass high frequency point
For 50Hz output frequency models:
51-55Hz: setting the frequency high loss point from 51Hz to 55HZ(Default:
53.0Hz)
For 60Hz output frequency models:
61-65Hz: setting the frequency high loss point from 61Hz to 65Hz(Default:
63.0Hz)
LLS: Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz: setting the frequency low loss point from 45Hz to
49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz: setting the frequency low loss point from 55Hz to
59Hz(Default: 57.0Hz)
Settings
Parameter 2: Enable or disable programmable outlets.
ENA: Programmable outlets enable
DIS: Programmable outlets disable (Default)
Settings
Parameter 2: Set up backup time limits for programmable outlets.
0-999: setting the backup time limits in minutes from 0-999 for program-
mable outlets which connect to non-critical devices on battery mode.
(Default: 999)
Uninterruptible Power Supply
Page 21