T91 User's Manual
Interface
04: ECO enable/disable
Interface
05: ECO voltage range setting
Interface
Xtreme Power Conversion Corporation
Settings
Parameter 2: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode is enabled, you may choose the following output fre-
quency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz
Settings
Parameter 2: Enable or disable ECO function. You may choose the fol-
lowing two options:
ENA: ECO mode enable
DIS: ECO mode disable (Default)
Settings
Parameter 2: Set the acceptable high voltage point and low voltage
point for ECO mode by pressing Down key or Up key.
HLS: High loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in parameter 3
is from +7V to +24V of the nominal voltage. (Default: +12V)
For 100/110/115/120/127 VAC models, the setting range in parameter 3
is from +3V to +12V of the nominal voltage. (Default: +6V)
LLS: Low loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in parameter 3
is from -7V to -24V of the nominal voltage. (Default: -12V)
For 100/110/115/120/127 VAC models, the setting voltage in parameter
3 is from -3V to -12V of the nominal voltage. (Default: -6V)
Uninterruptible Power Supply
Page 19