Xtreme Power Conversion 1000VA User & Installation Manual page 22

T91 unity
Hide thumbs Also See for 1000VA:
Table of Contents

Advertisement

T91 User's Manual
11: Autonomy limitation setting
Interface
12: Battery total AH setting
Interface
13: Maximum charger current setting
Interface
Xtreme Power Conversion Corporation
Settings
Parameter 2: Set up backup time on battery mode for general outlets.
0-999: setting the backup time in minutes from 0-999 for
general outlets on battery mode.
DIS: Disable the autonomy limitation and the backup time will depend
on battery capacity. (Default)
Note: When setting as "0", the backup time will be only 10 seconds.
Settings
Parameter 2: Set up the battery total AH of the UPS.
7-999: setting the battery total capacity from 7-999 in AH. Please set the
correct battery total capacity if external battery bank is connected.
Settings
Parameter 2: Set up the charger maximum current. For low voltage
model with 24/36/48VDC
1/2/4/6/8: setting the charger maximum current
1/2/4/6/8 in Ampere. (Default: 2A)
For high voltage model with 24/36/48VDC
1/2/4/6/8/10/12: setting the charger maximum current
1/2/4/6/8/10/12 in Ampere. (Default: 2A)
For low voltage and high voltage model with 72/96VDC
1/2/4/6/8: setting the charger maximum current
1/2/4/6/8 in Ampere. (Default: 2A)
Note: Please set the appropriate charger current based on battery ca-
pacity used. The recommended charging current is 0.1C~0.3C of battery
capacity as following table for
reference.
Battery capacity(AH)
7~20
20~40
40~60
60~80
80~100
100~150
Uninterruptible Power Supply
Total charging current (A)
2
4
6
8
10
12
Page 22