T91 User's Manual
06: Bypass enable/disable when UPS is off
Interface
07: Bypass voltage range setting
Interface
Xtreme Power Conversion Corporation
Settings
Parameter 2: Enable or disable Bypass function. You may choose the
following two options:
ENA: Bypass enable
DIS: Bypass disable (Default)
Settings
Parameter 2: Set the acceptable high voltage point and acceptable low
voltage point for Bypass mode by pressing the Down key or Up key.
HLS: Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3 from 230Vac to
264Vac. (Default: 264Vac)
For 100/110/115/120/127 VAC models:
120-140: setting the high voltage point in parameter 3 from 120Vac to
140Vac. (Default: 132Vac)
LLS: Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3 from 170Vac to
220Vac. (Default: 170Vac) For 100/110/115/120/127 VAC models:
85-115: setting the low voltage point in parameter 3 from 85Vac to
115Vac. (Default: 85Vac)
Uninterruptible Power Supply
Page 20