Saving The Provisioning Setup; Checking Alarm Status; Overview Of The Ssu-2000 Security System - Symmetricom SSU-2000 User Manual

Synchronization supply unit and the synchronization distribution unit
Hide thumbs Also See for SSU-2000:
Table of Contents

Advertisement

Provisioning and Operating the SSU-2000

Checking Alarm Status

Saving the Provisioning Setup

After you provision each module, you can save the setup in the Communications
module memory.
ICS command:
Type
SET SAVE
TL1 command:
SET-PRMTR-SETUP::ALL:123::SAVE;
Checking Alarm Status
All alarm indication lights should be extinguished and the POWER indication lights
should be green after completing the power up sequence. The valid input reference
alarm clears, rubidium lock clears, frequency alarms clear, and the ACQUIRE LED
is ON. Use the following procedure with the STATUS and ALARM commands to
verify that the unit is operational.
1. Connect a computer to the SSU-2000 using the procedure in
Connection With the
2. Log in to the SSU-2000:
ICS command:
Type
login
system prompts for a password. Type the administrator's password and press
Enter. The system prompt
TL1 command:
Type
ACT-USER::uid:123::pwd;
user id and password, respectively; 123 is an arbitrary ctag value.
3. Type
alarm
4. Type
bye

Overview of the SSU-2000 Security System

The SSU-2000 security system software contains a hierarchy of user levels that
permit an increasing level of access to system parameters. This allows the system
administrator to add users that can, for example, view but not change system
parameters; other users can view and change system parameters.
98
SSU-2000 User's Guide
, then press Enter.
SSU-2000, on page 88. The
followed by the administrator's user name and press Enter. The
SSU-2000>
and press the Enter key to verify that there are no active alarms.
and press the Enter key to log off the system.
SSU-2000>
appears.
where
and
are the administrator's
uid
pwd
12713020-002-2 Revision D – April 2004
Establishing a
prompt appears.