Exchanging A Module - Symmetricom SSU-2000 User Manual

Synchronization supply unit and the synchronization distribution unit
Hide thumbs Also See for SSU-2000:
Table of Contents

Advertisement

Installing the SSU-2000
Handling Modules
1. Align the module card edges with the plastic card guides of the selected slot.
2. Slide the module into the shelf until it seats fully into its rear panel edge
connector.
3. Tighten the captive screws located at the top and bottom of the module front
panel.
Caution: To avoid possible damage and intermittent failures, ensure
that you have completely inserted the module into the system and
that you have securely tightened the captive screws.
4. Enable the module using either ICS or TL1 commands. The example
commands are for slot 3 in the main shelf.
ICS command:
Type
CONFIG 1A3 ENABLE
TL1 command:
ACT-MODULE::S1A3:123;

Exchanging a Module

Use this procedure to exchange one type of module with the same type or a
different type of module in the same slot. The example commands are for slot 3 in
the main shelf.
1. Connect to the SSU-2000 using one of the methods described in
Connection With the
name.
2. Log in to the system using your user name and password.
3. Disable the module using either ICS or TL1 commands. The example
commands are for slot 3 in the main shelf.
ICS command:
Type
CONFIG 1A3 DISABLE
TL1 command:
DISC-MODULE::S1A3:123;
4. Loosen the captive screws located at the top and bottom of the module front
panel.
5. Pull up on the top extractor and down on the bottom extractor to unseat the
module from the connector on the backplane.
6. Slide the module out of the shelf.
80
SSU-2000 User's Guide
, then press Enter.
SSU-2000, on page 88. The system prompts for a user
, then press Enter.
Establishing a
12713020-002-2 Revision D – April 2004