Installing the SSU-2000
Making Connections
Power Input
1. Locate the power terminal blocks on the rear panel, as shown in
2. Remove both 5 A fuses. You will replace them at the end of the installation
procedure.
3. Using 16 AWG (minimum) stranded wire, connect primary power to the A-BUS
screws and the secondary power to the B-BUS screws. Symmetricom
recommends that you use a #6 spade lug termination for each power lead.
Figure 2-3.
Power Terminal Blocks
Making Connections
Making I/O Connections
The SSU-2000 shelf has I/O interface connections for connecting the SSU-2000 to
the corresponding I/O adapter panels. Refer to
Data, and
Chapter 8, Output Module Reference Data,
different type I/O adapter panels available and the associated cables used to
connect the SSU-2000 to the I/O adapter panels.
the SSU-2000.
66
SSU-2000 User's Guide
Figure
Chapter 7, Input Module Reference
for information regarding the
Figure 2-4
shows the rear panel of
12713020-002-2 Revision D – April 2004
2-3.