Atomised Water Distribution; Atomised Water Distributor; Fan Conveyor; Elbow Connector - Carel HUMISONIC User Manual

Ultrasound humidifier
Hide thumbs Also See for HUMISONIC:
Table of Contents

Advertisement

Available languages

Available languages

ENG

3.1 Atomised water distributor

Important:
the atomised water delivery hose, the distributor, the fan
conveyor, the elbow connection and the diff user are not supplied with the
humidifi er.
Code
UUKDP02500
UUKDP05300
UUKDP06100
UUKDP08500
Requirements:
humidifi er delivery hose Øext 40mm ;
make sure the atomised water outlet area is 1100 mm2 (e.g. 22 holes
8 mm in diameter);
if the customer has to provide a distributor with diff erent length, it is
important to respect a maximum length of 1m. For greater lengths,
please contact the Service Department Carel;
the hose running to the distributor should have a minimum upward
gradient of 2° so that any condensate fl ows back into the humidifi er or
a special condensate drain system;
make sure there are no condensate leaks from the water vapour
distributor;
position the distributor in such a way that the air is not directed against
nearby objects (minimum distance 10 cm);
bends or choking of the hose may cause condensate to form and
decrease humidity delivery;
avoid loads that may cause mechanical stress on the humidifi er outlet
connector.
"Ultrasound for fancoil" +0300059IE - rel. 1.1 - 29.01.2016
3.

ATOMISED WATER DISTRIBUTION

Lenght (mm)
250
530
610
850
Fig. 3.a
Fig. 3.b

3.2 Fan conveyor

The air fl ow conveyor can be installed on the top of the fan (removing
the protection grill) so as to take in air from a diff erent place to where
humiSonic is installed.

3.3 Elbow connector

The elbow connector can be installed on the cover and/or the fan conveyor,
so as to reduce the overall height occupied by the product.
3.4
Diff user
The diff user can be installed on the cover, so as to deliver atomised water
directly into the room.

3.5 Filter: 50 micron

A fi lter is available to be installed on the fan, using the conveyor (with or
without the elbow). The fi lter is delivered disassembled (cap not fi xed)
because on one side it is possible to mount it on the conveyor, on the other
side on the elbow (to mount with a slight interference). Once mounted,
insert the cap. It's necessary to clean the fi lter (with compressed air or
running water) periodically: frequency depends on the environment in
which the system is installed. Features fi lter: 50 micron, H = 13 cm, D = 5 cm
10
Fig. 3.c
Fig. 3.d
Fig. 3.e
Fig. 3.f

Advertisement

Chapters

Table of Contents
loading

Table of Contents