Configuration Parameters; Basic Parameters; Advanced Parameters; Accessing And Setting Parameters - Carel HUMISONIC User Manual

Ultrasound humidifier
Hide thumbs Also See for HUMISONIC:
Table of Contents

Advertisement

Available languages

Available languages

ENG

6.6 Accessing and setting parameters

The confi guration parameters can be used to set and control humidifi er
functions and status.
From the main screen press:
ENTER for 2 seconds,
enter the password 77 using UP or DOWN,
ENTER to confi rm and access the list of parameters,
UP or DOWN to scroll the list,
ENTER to select a parameter (display: 'set'),
UP to modify (increase) the value of the parameter. To scroll faster press
DOWN together,
DOWN to modify (decrease) the value of the parameter. To scroll faster
press UP together,
ENTER to save the new value and return to the list of parameters, or ESC
to return to the list without saving the value,
Press ESC to return to the main screen.
To access and set the following parameters, see chapters 6 and 12.

7.1 Basic parameters

Parameter
A0
Operating mode
0 = On/Off mode from auxiliary card probe input
1 = Proportional mode from auxiliary probe input
2 = Humidity probe mode from auxiliary card probe input
3 = Auto mode: if fi tted, humidity probe TH reading is used, otherwise On/Off mode from contact on main
board. Parameter A2 is not used
A1
Unit of measure 0 = Celsius ; 1= Fahrenheit
A2
Type of external sensor (optional card) (0 = On/Off ; 1 = 0-10V; 2 = 2-10V; 3 = 0-20 mA; 4 = 4-20 mA)
P0
Maximum production
(1)
P1
Humidity control hysteresis
St
Default display (Terminal)
C0
Default display (Terminal) 0 = Probe reading/control signal; 1 = P0 maximum production; 2 = Hour counter

7.2 Advanced parameters

Parameter
A3
Probe minimum
A4
Probe maximum
A5
Probe off set
A6
Fan off delay time
A7
Fan speed
A8
Maximum evaporation time for reduced production alarm
A9
Minimum evaporation time for reduced production alarm
AA
Retry waiting time
Ab
Percentage of A8 at which to run the level test
AC
Maximum time to measure level when refi lling
Ad
Maximum time to measure high level
AE
Fan restart time in standby on built-in probe reading
b0
Operating options (see table of parameter b0 values)
b1
Time between two washing cycles
b2
Inactivity time for washing
b3
Washing time (fi ll + drain)
b4
Start delay time
b5
Operating hours for CL alarm
b6
Time to display new CL alarm after reset from keypad (without resetting hour counter)
b7
Transducer modulating control period
b8
Probe disconnected delay
b9
Reserved
bA
Maximum fi ll time
bb
Water refi ll time in production
bC
Maximum drain time
bd
Drain opening time to completely empty tank
bE
Delay time after measuring low level for refi lling
bf
Drain activation delay in standby (if drain solenoid valve in standby = OPEN)
P1
Humidity control hysteresis
P2
Low humidity alarm threshold
P3
High humidity alarm threshold
(1) To change the value from the terminal it is necessary set all related dipswitch to Off . To again use the value given by the dipswitch it is necessary set one of the dipswitch to On and
power off . At the next reboot the control will use again the values set by the dipswitch.
(*) after 999 the display shows
(**) the default is equal to 0 (zero), for humidifi ers without auxiliary card and without humidity/temperature probe.
"Ultrasound for fancoil" +0300059IE - rel. 1.1 - 29.01.2016
7.

CONFIGURATION PARAMETERS

to indicate the 1000s (the three digits are displayed with a dot at the top between the fi rst and second digit).

6.7 Parameters: Recall default values

The default values of the parameters can be recalled at any time from the
main screen.
From the main screen press:
ENTER for 2 seconds,
enter the password 50 using UP or DOWN and press ENTER,
The message dEF fl ashes: to recall the default values press ENTER, or
ESC to exit.
If no button is pressed for 30 seconds, the display returns to the main
screen without recalling the default values.

6.8 Reset hour counter from display

Access parameter 'd3' (see Chap. 7)
press UP and DOWN for 5 seconds
When reset is complete, 'res' is shown on the display.
UOM range
-
-
-
%
10...100 100
%rH
%rH
-
UOM
%rH
%rH
%rH
min
min
min
min
min
min/h
min
min
%rH
%rH
%rH
16
def
note
0...3
3
0...1
0
0...4
1
only if terminal connected, other-
wise values set by dipswitch
2...20
2
20...80
50
only if terminal connected, other-
wise values set by dipswitch
0...2
0
range
def
note
0...100
0
0...100
100
-99...100
0
0...240
5
%
40...100
100
0...200
30
0...200
1
1...60
10
%
50...90
70
s
1...60
10
s
1...60
10
0...120
10(**)
-
0...255
7
0...120
60
h
0...240
24
0...10
1
s
0...240
10
h
0...3000(*)
1500
m
0...240
60
s
0...10
1
s
0...200
10
s
0...60
2
m
0...30
15
s
0...120
10
s
0...240
60
s
0...240
30
s
0...240
20
0...60
0
2...20
2
0...100
20
0...100
80
Tab. 7.a
Tab. 7.b

Advertisement

Chapters

Table of Contents
loading

Table of Contents