3.1 Atomised water distributor
Important:
Important:
the atomised water delivery hose, the distributor, the
fan conveyor, the elbow connection and the diff user are not supplied with
the humidifi er.
Requirements:
humidifi er delivery hose OD 40 mm;
make sure the atomised water outlet area is 1100 mm2 (e.g. 22 holes
8 mm in diameter);
the hose running to the distributor should have a minimum upward
gradient of 2° so that any condensate fl ows back into the humidifi er or
a special condensate drain system;
make sure there are no condensate leaks from the water vapour
distributor;
position the distributor in such a way that the air is not directed against
nearby objects (minimum distance 10 cm);
bends or choking of the hose may cause condensate to form and
decrease humidity delivery;
avoid loads that may cause mechanical stress on the humidifi er outlet
connector.
3.2 Fan conveyor
The air fl ow conveyor can be installed on the top of the fan (removing
the protection grill) so as to take in air from a diff erent place to where
humiSonic is installed.
"Ultrasound humidifi er for fan coils" +0300056EN - rel. 1.5 - 24.06.2015
3.

ATOMISED WATER DISTRIBUTION

Fig. 3.a
Fig. 3.b
Fig. 3.c
3.3 Elbow connector
The elbow connector can be installed on the cover and/or the fan conveyor,
so as to reduce the overall height occupied by the product.
3.4
Diff user
The diff user can be installed on the cover, so as to deliver atomised water
directly into the room.
3.5 Filter: 50 micron
A fi lter is available to be installed on the fan, using the conveyor (with or
without the elbow). The fi lter is delivered disassembled (cap not fi xed)
because on one side it is possible to mount it on the conveyor, on the other
side on the elbow (to mount with a slight interference). Once mounted,
insert the cap. It's necessary to clean the fi lter (with compressed air or
running water) periodically: frequency depends on the environment in
which the system is installed. Features fi lter: 50 micron, H = 13 cm, D = 5 cm