Parameters/address space
4.1
Parameters
DI 8xNAMUR HF parameters
The following table lists the configurable parameters. The effective range of the configurable
parameters depends on the type of configuration. The following configurations are possible:
● Distributed operation on PROFINET IO in an ET 200SP system
● Distributed operation with PROFIBUS DP in an ET 200SP system
When assigning parameters in the user program, use the "WRREC" instruction to transfer
the parameters to the module using data records (refer to the section Parameter assignment
and structure of parameter data record (Page 33)).
The following parameter settings are possible:
Table 4- 1
Configurable parameters and their defaults (GSD file)
Parameters
Diagnostics:
•
Missing supply
•
voltage L+
Diagnostics:
•
Short-circuit to
•
ground
Diagnostics:
•
Wire break
•
Diagnostics:
•
Changeover error
•
Diagnostics:
•
Chatter error
•
Chatter monitoring:
•
Monitoring window
•
Chatter monitoring:
•
Number of signal
•
changes
DI 8xNAMUR HF digital input module (6ES7131-6TF00-0CA0)
Manual, 02/2014, A5E03894478-01
Value range
Disable
Disable
Enable
Disable
Disable
Enable
Disable
Disable
Enable
Disable
Disable
Enable
Disable
Disable
Enable
0.5 s
0.5 s
1 s to 100 s (can be
set in 1 s-increments)
Deactivated
Deactivated
2 to 32
Default
Changing
parameter
settings in RUN
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Effective range with configuration
software, e.g. STEP 7 (TIA-Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
-
Channel
-
Channel
-
4
11