order to reach the scheduled temperature at the scheduled time. (When the unit starts the first time after
power reset, the operation starts 30 minutes before the scheduled time.) When using this function, also set
the operation mode and setting temperature. If "Prohibit Remote Controller" is set at the same time, remote
controller is prohibited at its setting time.
If the room temperature is measured by the air-conditioner's suction temperature sensor, the temperature
may not be correct when the air-conditioner is inactive and the air is not fresh. When the temperature is not
measured correctly, switch the sensor to external temperature sensor (PAC-SE40TSA) or remote control
sensor.
Note: Only air conditioner units can set [Optimized start].
Note: The CITY MULTI model supports a temperature setting range of 12-28°C / 53-83°F when in Heat mode.
(When S series (PUMY) is used, set the temperature at 17°C-28°C / 63-83°F in heat mode.)
Note: When setting a schedule for all groups or for a block, it is possible to set all operation modes such as Auto mode
etc, but if some targeted air conditioner units do not have such a function, then those units will not run in the
specified mode. When setting the schedule, consider what functions are supported by the air conditioner units.
Note: When setting a schedule for all groups or for a block, it is possible to set prohibit remote controller items
individually. When allowing remote controller operation under K control, however, all items must be set
enable.
Note: When setting a schedule for ventilator units, the temperature setting and fan direction is not displayed.
Moreover, the prohibit remote controller operation is simply [ON/OFF].
Note: When setting a schedule for Air To Water (PWFY) units, the fan direction setting and fan speed setting is are
not displayed.
Note: Only the ON/OFF operation is possible on the general equipment.
(3)Copy a schedule to another group
When copying a schedule of the day between each group, click [Copy
(Group)]. The color of the button turns to green (which means the
button is selected). Select the desired group, and click [Paste] button.
Note: Copied schedule cannot be pasted to different type of
equipment. For example, schedule copied on the air conditioner
cannot be pasted to the ventilator equipment.
Note: The operation mode that can be pasted and the temperature
setting range vary depending on the unit type.
(4)Save the contents of schedule
After you have finished setting the contents of the schedule, save the
schedule setting by clicking the [Save Settings] button.
If the contents of the schedule setting have changed since the
previous save, you can click the [Undo] button to restore the setting
contents back to the saved settings.
Save Settings button
39
Copy (Group) / Paste

Advertisement